Operator Procedures
Ctrl Nr: PM375118-004
81
13
Operator Procedures
Once configured, the STS requires few operator interventions. The following procedures cover the main
interventions.
13.1
Startup after Power Rework
Initial startup is covered in
4.1.3 Commissioning: Initial Power-up Site Test
. If power rework has been
performed upstream of the STS, follow steps 2-4 of this procedure to verify correct input power to the
STS.
13.2
Normal Startup
Powering up the STS for normal operation can be done as follows:
1. The STS should be left in Normal mode configuration for MCCBs and MCSWs as shown in
Figure 6, Normal Mode MCCB/MCSW Configuration.
2. Apply power to the STS externally by closing circuit breakers feeding the unit.
13.3
Restarting the Monitor
When the Ethernet settings are changed on the
Settings
screen (
10.2 Ethernet
), the Monitor must be
restarted. Because the Monitor logic controls transfers, the STS must briefly be put in Redundant Mode to
provide a backup transfer capability to the Monitor:
1. On the
Home
screen, make note of the existing parameters, particularly
Preferred Source
and the actively conducting source as indicating by the
yellow line
on the One-line display.
2. Use the STS key to open the left-side doors in front of the display. Open the ROI panel.
3. On the ROI, set the
MODE OF OPERATION
toggle switch to
REDUNDANT
mode.
4. Login on the
Home
page as Administrator or other higher level authorization.
5. In the navigation buttons, touch the
Setup
button to display the
Settings
screen.
6. In the
Ethernet Settings
panel, touch the
Restart
button to restart the Monitor. Touch the
button just once: the restart will take around 30-45 seconds and it is not immediately
apparent that the restart is proceeding.
7. When the
Home
screen reappears, do a visual check of Monitor parameters and settings for
correctness:
a. On the dynamic One-line display, verify that the currently conducting source matches
the source indicated by yellow line.
b. Verify that the
Preferred Source
selector is selecting the currently conducting
source. (If the
Preferred Source
selector is not the current source, it will force a
transfer when you return to
NORMAL
mode.)
c. If the
Preferred Source
is
not
the currently conducting source, login on the
Home
screen with at least operator-level authorization and set the
Preferred Source
selector to the source recorded in step 1.
8. After validating the Monitor, at the ROI set the
MODE OF OPERATION
toggle switch to
NORMAL
mode.
9. Close and lock the STS doors.
Содержание WaveStar 2000A
Страница 1: ...WaveStar Static Transfer Switch 2000A 3 Pole Installation and Operation Ctrl Nr DOC15139 Revision 004 ...
Страница 13: ...System Description Ctrl Nr PM375118 004 13 Figure 5 STS 2000A 3 Pole One line Diagram ...
Страница 25: ...Installation Planning Ctrl Nr PM375118 004 25 Figure 9 General Assembly Drawing Customer Power Connections ...
Страница 66: ...WaveStar Static Transfer Switch 2000A 3 Pole 66 Ctrl Nr PM375118 004 Touch Reset to reset the modem ...
Страница 76: ...WaveStar Static Transfer Switch 2000A 3 Pole 76 Ctrl Nr PM375118 004 Figure 36 Help Procedure Examples ...