WaveStar Static Transfer Switch 2000A 3-Pole
28
Ctrl Nr: PM375118-004
4
Installation and Startup Procedures
Installation is the responsibility of the Installer, who may be an Installing Contractor. The Installer must be
an electrician certified for the locality where the installation is being performed.
A PDI-certified technician must perform or witness Commissioning and Start-up of the STS 2000A unit to
validate the warranty.
4.1
Installation Instructions
4.1.1
Positioning the STS 2000A Unit
The stand-alone STS 2000A requires front access for normal operation and both front and rear access for
installation and maintenance.
1. The standalone STS 2000A requires 30" front and rear access for installation and maintenance,
allowing the unit to be fully serviced and complying with the 1996 National Electric Code for
access to Circuit Breaker distribution equipment.
2. Check STS floor loading to verify that the STS 2000A system does not exceed the raised floor
loading specifications. System weight and cabinet dimensions are given in
2.1 System
Enclosure
.
3. If additional raised floor supports are required, contact PDI at 1-800-225-4838 or your raised floor
manufacturer for either floor jacks or full frame floor stands and their specifications.
4. The STS 2000A does not have casters or leveling feet because of the weight of the unit.
DANGER!
•
Severe or fatal injury can result from electrical shock during contact with high
voltage conductors, monitoring PCBs, or similar equipment.
•
Disconnect power before drilling holes, attaching cables or conduit, or
connecting PDUs to other power distribution equipment.
•
Use Lock Out/Tag Out procedures.
•
Wear suitable personal protective clothing and use protective equipment for
performing mechanical and electrical installations.
•
Leave ample space for attaching and routing wires.
IMPORTANT!
•
A licensed electrician must install each unit.
•
Startup by a PDI certified technician is required to validate the warranty.
•
To validate the warranty, please complete the Warranty Validation Request
form and notify PDI Service Department upon completion of the startup to
initiate the Warranty Coverage.
Содержание WaveStar 2000A
Страница 1: ...WaveStar Static Transfer Switch 2000A 3 Pole Installation and Operation Ctrl Nr DOC15139 Revision 004 ...
Страница 13: ...System Description Ctrl Nr PM375118 004 13 Figure 5 STS 2000A 3 Pole One line Diagram ...
Страница 25: ...Installation Planning Ctrl Nr PM375118 004 25 Figure 9 General Assembly Drawing Customer Power Connections ...
Страница 66: ...WaveStar Static Transfer Switch 2000A 3 Pole 66 Ctrl Nr PM375118 004 Touch Reset to reset the modem ...
Страница 76: ...WaveStar Static Transfer Switch 2000A 3 Pole 76 Ctrl Nr PM375118 004 Figure 36 Help Procedure Examples ...