OAFE-2000
IO&M Manual
Paragon Controls Incorporated
40
Revision Level 000
Object
Object Name (max 32
Char)
Cr
ea
te
Obje
ct
Servic
e
Delete Object
Servic
e
Optional
Properties
Supported
Writeable
Properties
Property Data
Type
Data Value
Description
(State Text)
Note: Unit Selection Dependent on Multi State Value-11
Multi State
Value-4
Temperature
Engineering Units
No
No
• Description
R/W
UNSIGNED
1: F°
2: C°
Multi State
Value-5
System 1 Temperature
Source
No
No
• Description
R/W
UNSIGNED
1: Fixed
2: Analog
3: Network
Multi State
Value-6
System 2 Temperature
Source
No
No
• Description
R/W
UNSIGNED
1: Fixed
2: Analog
3: Network
Multi State
Value-7
System 3 Temperature
Source
No
No
• Description
R/W
UNSIGNED
1: Fixed
2: Analog
3: Network
Multi State
Value-9
System 1 Process Type
No
No
• Description
R/W
UNSIGNED
1: Standard Flow
2: Actual Flow
3: Standard
Velocity
4: Actual Velocity
5: Pressure
Multi State
Value-10
System 2 Process Type
No
No
• Description
R/W
UNSIGNED
1: Standard Flow
2: Actual Flow
3: Standard
Velocity
4: Actual Velocity
5: Pressure
Multi State
Value-11
System 3 Process Type
No
No
• Description
R/W
UNSIGNED
1: Standard Flow
2: Actual Flow
3: Standard
Velocity
4: Actual Velocity
5: Pressure
Multi State
Value-12
DP1 Alarm Enable
No
No
• Description
R/W
UNSIGNED
1 = Off
2 = Low
3 = High
Multi State
Value-13
DP2 Alarm Enable
No
No
• Description
R/W
UNSIGNED
1 = Off
2 = Low
3 = High
Multi State
Value-14
DP3 Alarm Enable
No
No
• Description
R/W
UNSIGNED
1 = Off
2 = Low
3 = High
Multi State
Value-15
DP4 Alarm Enable
No
No
• Description
R/W
UNSIGNED
1 = Off
2 = Low
3 = High
CharacterString
Value-1
System 1 Tag
No
No
• Description
R/W
STRING
CharacterString
Value-2
System 2 Tag
No
No
• Description
R/W
STRING
CharacterString
Value-3
System 3 Tag
No
No
• Description
R/W
STRING
CharacterString
Value-4
Sub System Tag
No
No
• Description
R/W
STRING
Analog Input-21
System 1 Sensor 1 Flow
No
No
• Description
• Eng Units
R
REAL
Analog Input-22
System 1 Sensor 1
Pressure
No
No
• Description
• Eng Units
R REAL