OAFE-2000
IO&M Manual
Paragon Controls Incorporated
37
Revision Level 000
MTSE Unit BACnet Protocol Implementation Conformance
Statement
Rev 7 3/31/22
BACnet Standardized Device Profile (Annex L):
BACnet Application Specific Controller (B-ASC)
BACnet Interoperability Building Blocks Supported (Annex K):
DS-RP-B
DS-RPM-B
DS-WP-B
DS-WPM-B
DM-DDB-B
DM-DOB-B
DM-DCC-B
Segmentation Capability:
NONE
Standard Object Types Supported:
Analog Input
Analog Value
Binary Input
Binary Value
Multistate Input
Multistate Value
CharacterString Value
Data Link Layer Options:
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400, 76800
Device Address Binding:
NO
Networking Options:
NONE
Character Sets Supported:
ISO 10646 (UTF-8), ANSI 3.4
Supported Services:
ReadProperty Execute
ReadPropertyMultiple Execute
WriteProperty Execute
WritePropertyMultiple Execute
DeviceCommunicationControl Execute
Who-Is Execute
I-Am Initiate
Who-Has
Execute
I-Have Initiate
Gateway:
This product does not support gateway functionality for any types of non-BACnet equipment/network(s).