29
TROUBLESHOOTING
Figure 9.1: Intermittent Ignition System Troubleshooting Sequence
NOTE: “CALL FOR HEAT” 24 VAC SUPPLY IS CONNECTED TO THE 24 V TERMINAL ON THE CONTROL.
TURN GAS SUPPLY OFF,
TURN THERMOSTAT
(CONTROLLER) TO
“CALL FOR HEAT.”
POWER TO
MODULE? (24 V
NOMINAL)
SPARK
ACROSS
IGNITER/
SENSOR
GAP?
PILOT BURNER
LIGHTS?
SPARK
STOPS WHEN
PILOT IS
LIT?
SYSTEM
SHUTS
OFF?
SYSTEM
RUNS UNTIL “CALL
FOR HEAT”
ENDS?
MAIN BURNER
LIGHTS?
TURN GAS SUPPLY
ON AND RECYCLE
“CALL FOR HEAT.”
“CALL FOR HEAT” ENDS
CHECK LINE VOLTAGE POWER, LOW VOLTAGE TRANSFORMER, LIMIT CONTROLLER, THERMOSTAT (CONTROLLER), AND WIRING ALSO.
CHECK AIR PROVING SWITCH ON COMBUSTION AIR BLOWER SYSTEM (IF USED) AND THAT THE VENT DAMPER END SWITCH (IF USED)
IS MADE.
CHECK IGNITION CABLE, GROUND WIRING, CERAMIC INSULATOR, AND SPARK GAP ARE CORRECT.
CHECK BOOT OF THE IGNITION CABLE FOR SIGNS OF MELTING OR BUCKLING, TAKE PROTECTIVE ACTION TO SHIELD CABLE
AND BOOT FROM EXCESSIVE TEMPERATURES.
CHECK THAT ALL MANUAL GAS VALVES ARE OPEN, SUPPLY TUBING AND PRESSURES ARE GOOD, AND PILOT BURNER
ORIFICE IS NOT BLOCKED (PILOT GAS FLOWING).
CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND PILOT OPERATOR ON GAS CONTROL.
CHECK FOR 24 VAC ACROSS PV-MV/PV TERMINALS ON MODULE. IF VOLTAGE IS OKAY, REPLACE GAS CONTROL.
IF NOT, REPLACE MODULE.
NOTE: IT MAY BE NECESSARY TO RECYCLE THE ‘CALL FOR HEAT” MORE THAN ONCE TO CLEAR THE PILOT SUPPLY TUBES OF AIR.
NOTE: IF CONTROL GOES INTO LOCKOUT OR RETRY DELAY, RESET THE “CALL FOR HEAT.”
CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE.
CLEAN FLAME ROD.
CHECK ELECTRICAL CONNECTIONS BETWEEN FLAME ROD AND MODULE.
CHECK FOR CRACKED CERAMIC FLAME ROD INSULATOR.
CHECK THAT PILOT FLAME COVERS FLAME ROD AND IS STEADY AND BLUE.
ADJUST PILOT FLAME.
IF PROBLEM PERSISTS REPLACE MODULE.
CHECK FOR 24 VAC ACROSS PV-MV/PV TERMINALS ON MODULE. IF NO VOLTAGE, REPLACE MODULE.
CHECK ELECTRICAL CONNECTIONS BETWEEN MODULE AND GAS CONTROL INCLUDING SAFETY CONTROLS WIRED IN THE CIRCUIT.
IF OKAY, REPLACE GAS CONTROL.
NOTE: IF CONTROL GOES INTO LOCKOUT OR RETRY DELAY, RESET THE “CALL FOR HEAT.”
CHECK CONTINUITY OF IGNITION CABLE AND GROUND WIRE.
NOTE: IF GROUND IS POOR OR ERRATIC, SHUTDOWNS MAY OCCUR OCCASIONALLY EVEN THOUGH OPERATION IS NORMAL
AT THE TIME OF CHECKOUT.
CHECK THAT PILOT FLAME COVERS FLAME ROD AND IS STEADY AND BLUE, PILOT FLAME MUST NOT BE MOVING AROUND DUE TO
OUTSIDE AIR FLOWS, ETC.
ADJUST PILOT FLAME. CHECK GAS PRESSURE MEETS APPLIANCE SPECIFICATIONS WHILE APPLIANCE MAIN BURNER ON AND ALL
OTHER GAS APPLIANCES ON THE SUPPLY ARE OPERATING AT FULL RATE.
IF CHECKS ARE OKAY, REPLACE MODULE.
CHECK FOR PROPER THERMOSTAT (CONTROLLER) OPERATION.
REMOVE MV LEAD AT MODULE, IF VALVE CLOSES, RECHECK TEMPERATURE CONTROLLER AND WIRING. IF NOT, REPLACE
GAS CONTROL.
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
YES
YES
NO
PULL IGNITION LEAD AND
CHECK SPARK AT MODULE.
SPARK OK?
NO
REPLACE MODULE
YES
START
BEFORE TROUBLESHOOTING,
FAMILIARIZE YOURSELF WITH
THE STARTUP AND
CHECKOUT PROCEDURES.
REPEAT PROCEDURE UNTIL
TROUBLE FREE OPERATION
IS OBTAINED.
NO
Содержание Peerless Boilers GM Series
Страница 1: ...GM Boilers Series Gas Installation Operation Maintenance Manual...
Страница 21: ...19 ELECTRICAL Figure 6 2 Wiring Diagram Spark Ignited Pilot Hydrolevel 3200 Limit control...
Страница 25: ...23 Figure 8 3 Operating Instructions Spark Intermittent Ignition START UP PROCEDURES...
Страница 26: ...24 START UP PROCEDURES Figure 8 4 Operating Instructions Spark Intermittent Ignition...
Страница 38: ...REPAIR PARTS Figure 12 3a Figure 12 3b 36...
Страница 40: ...REPAIR PARTS 13 14 15 16 17 24 25 22 21 20 19 18 23 Figure 12 4 38...
Страница 42: ...NOTES 40...