20
B. SEQUENCE OF OPERATION,
INTERMITTENT IGNITION
1. Thermostat calls for heat.
2. Limit senses boiler water temperature. Prevents
operation until water temperature falls approximately
15°F (9°C) below the cut-out temperature.
3. Automatic vent damper (if used) opens. Damper
must be in open position when appliance main
burner(s) is operating.
4. Gas valve energizes.
a. Igniter on.
b. Pilot gas on, igniting pilot.
5. Pilot flame detected.
a. Igniter off.
b. Main gas on, igniting main burners.
Note: If the pilot is not detected within 90 seconds, the
igniter and pilot gas are turned off for 5 minutes. The
sequence then resumes at Step 4a.
6. Call for heat ends.
a. Pilot and main gas off, extinguishing pilot and
main burners.
b. Automatic vent damper (if used) closes.
ELECTRICAL
Содержание Peerless Boilers GM Series
Страница 1: ...GM Boilers Series Gas Installation Operation Maintenance Manual...
Страница 21: ...19 ELECTRICAL Figure 6 2 Wiring Diagram Spark Ignited Pilot Hydrolevel 3200 Limit control...
Страница 25: ...23 Figure 8 3 Operating Instructions Spark Intermittent Ignition START UP PROCEDURES...
Страница 26: ...24 START UP PROCEDURES Figure 8 4 Operating Instructions Spark Intermittent Ignition...
Страница 38: ...REPAIR PARTS Figure 12 3a Figure 12 3b 36...
Страница 40: ...REPAIR PARTS 13 14 15 16 17 24 25 22 21 20 19 18 23 Figure 12 4 38...
Страница 42: ...NOTES 40...