40
PAW5500-VES
EN
PAW5500-VES Compact systems
System manual
Charger
Battery charger
Battery confi guration panel.
By pressing ‘
Change
’ it is possible
to set:
- The capacity of the battery
(choose 18, 26, 33 or 40 Ah).
- ‘
Energy save
’ mode enabled
disabled. This enables the
batteries to remain in the
energy saving mode when
there is no mains power.
*
According to UNI ISO 7240-19
point 5.15.3 requirements:
24 h standby plus 30 minutes in vocal
alarm condition.
2 AMP (Pmax = 250W)
Capacity Duration without mains supply
18 Ah
24 h + 30 min*
26 Ah
35 h + 30 min
33 Ah
44 h + 30 min
40 Ah
72 h + 30 min
4/6 AMP (Pmax = 500W)
Capacity Duration without mains supply
26 Ah
24 h + 30 min*
33 Ah
30 h + 30 min
40 Ah
36 h + 30 min
Label
Application
See panel
Notes
More
Selection of optional cards
Local broadcasting unit
Panel enabling two selections to
be made:
- Optional cards
- Local unit con
fi
g.
On the ‘Optional cards’ screen,
press the >> key to select and
enable the optional card, if any,
present in the system (
ACPAW-
2IN
or
ACPAW-6IN
).
On the ‘Local unit confi g.’
screen, slide the cursors to
select up to 4 broadcast stations
to be used in the local mode
(included among the 16 that
are permitted). On activating
this function, keys 1 to 6 of the
station will correspond, in the
same order, to the zones of the
card-cage to which the station
itself is connected (e.g. if the
local base is connected to card-
cage 2, key 1 will correspond to
zone 13, key 2 to zone 14 and
so on). It is advisable to use
Paso
PMB106-G
units as local
stations.