17
EN
PAW5500-VES
System manual
PAW5500-VES Compact systems
4.2.11 CONNECTION OF POWER SUPPLIES
TERMINAL STRIP AND CHARGER
1> Check that the main thermal-magnetic circuit breaker is switched
OFF.
2> Connect the power cable coming from the thermal-magnetic circuit
breaker and the earth cable to the contacts on the terminal strip
(
A
) - see fi gure.
3> Connect the external terminals (
B
) of the batteries,
observing the correct polarities.
4> Switch the thermal-magnetic circuit breaker ON.
5> Make a jumper between the inside terminals of the
batteries using the cable (
C
) included in the supply.
6> Close the front door, tightening the screws fi rmly.
From now on the PAW is working.
NOTE:
If the front door is opened, the amplifi ers are deactivated
automatically, and can be re-activated by specialised
personnel only by using a specifi c menu item.
!
N.B.
Check that the main thermal-magnetic circuit breaker is switched
OFF. If it is not, switch it OFF before carrying out any other activities
in the cabinet as there is a danger of electric shocks.
!
N.B.
These devices have been designed to be connected to an earthed
power supply. Make sure that the equipment is always connected
to earth in accordance with legal regulations.
It is essential to follow the correct sequence for powering up the
equipment, failing which it could be damaged.