8.7 CRITERIA FOR MANAGING PRIORITIES IN EMERGENCY CONDITIONS
THE SYSTEM MANAGES EMERGENCY CONDITIONS ON THE BASIS OF TWO CRITERIA:
8.7.1 MANAGEMENT OF PRIORITIES ON THE BASIS OF HOW EMERGENCIES ARE ACTIVATED
There are two possible types of activation:
MANUAL EMERGENCY
: emergency state activated by the operator by means of the LED pushbutton on the card-cage
local controls or on the emergency microphone stations.
AUTOMATIC EMERGENCY
: emergency state activated from control inputs.
Depending on the management system, it is possible that only one operator can activate a MANUAL EMERGENCY; in this
case, the local controls of the card-cages have maximum priority.
In a system with more than one card-cage, the fi rst card-cage to activate the emergency has priority.
The emergency stations follow in the order of priorities, on the basis of the level set on the base itself.
The AUTOMATIC EMERGENCY condition, on the other hand, is always in addition to the MANUAL EMERGENCY, if any,
and, if necessary, it can be excluded by the latter.
8.7.2 MANAGEMENT OF PRIORITIES OF ALARM MESSAGES
When diff erent alarm messages are called up on a given zone from diff erent sources (local controls, remote microphone
stations, control inputs and remote card-cages), the system will choose the message to be sent out depending on how the
priorities are managed. The order of priority is indicated below, starting from the highest priority down to the lowest:
1. Handsfree messages from a local unit/ remote station / remote control unit (in this case all pre-recorded messages will be
muted).
2. EVACUATION message (message 1) activated by a MANUAL EMERGENCY.
3. ALERT message (message 2) activated by a MANUAL EMERGENCY.
4. Message 1 activated by an AUTOMATIC EMERGENCY.
5. Messages numbered from 3 to 8 in this order, with the EVAC attribute activated by an AUTOMATIC EMERGENCY.
6. Message 2 activated by an AUTOMATIC EMERGENCY.
7. Messages numbered from 3 to 8 in this order, with the ALERT attribute activated by an AUTOMATIC EMERGENCY.