
P
AGE
47
Service 5.1
This section contains Calibration, Test and Trouble-shooting procedures that can be
performed by the user. Instruments are calibrated to all input type specified when ordered at
the factory prior to shipment. Re-calibration should not be necessary under normal operating
conditions.
Calibration 5.2
Caution: Do not attempt any of these calibrations without the proper test equipment with specifications equal to or better
than those listed.
Press and release the SCROLL key to sequence the display until CAL appears. If CAL does
not appear, refer to Section 3 for instructions on how to enable the Calibration mode. When
CAL appears on the display, press the DOWN key. The display will read CAL 1. CAL 1 can
be initiated at this time or press the SCROLL key to advance the display to other calibrations
available.
CALIBRATION FLOW CHART
ON
OFF
Actual Display
On/Off Display -
Use arrow keys
to turn on or off
Scroll Key
Numeric Display -
Use arrow keys
to change value
Up Arrow Key
Down Arrow
Key
CAL2
CAL3
CAL4
CAL5
CAL6
CAL1
CAL
CAL7
Prog
CAL8
Содержание MIC 6000
Страница 1: ...Form 2854 Edition 10 December 1993 Installation Wiring Operation Manual MIC 6000 Brand ...
Страница 27: ...PAGE 27 PiA rrH PFF dFF Co1r Ptb Co2r Pout Pou PoL CCon CbS C C B Com Optional EO Option CAd ...
Страница 82: ...THE PARTLOW WEST COMPANY 2 CAMPION ROAD NEW HARTFORD NY 13413 USA 1 800 866 6659 315 797 2222 FAX 315 797 0403 ...