P
AGE
35
TABLE 3-3 PROFILE ENTRY MODE CONFIGURATION PROCEDURE
Depress and release the SCROLL key until PEnt is displayed. Use the DOWN key to enter
the Profile Entry mode. Depress the SCROLL key to scroll through the parameters and their
values. Use the UP and DOWN keys to adjust the values. After adjusting a parameter,
depress the SCROLL key to proceed to the next parameter. After all selections have been
made, to exit the mode, depress the UP key with a parameter in the display (not a setting).
For assistance in developing the Profile refer to Appendix F (page 78).
1
Profile Number
Pn
1 to 8
**
2
Number of Segments
nS
0-6 segments
**
Steps 3-11 are repeated for each segment
3
Ramp Time
rt
0 to 9999 units per Ptb
**
3
*Ramp Rate
rr
0 to 9999 units per Ptb
**
4
Setpoint
SP
Setpoint at end of Ramp
**
5
Event Output 1
E1
on or off
**
6
Event Output 2
E2
on or off
**
7
Event Output 3
E3
on or off
**
8
Soak Time
St
0 to 9999 units per Ptb
**
9
Event Output 1
E1
on or off
**
10
Event Output 2
E2
on or off
**
11
Event Output 3
E3
on or off
**
* Will be displayed instead of Ramp Time rt if Ramp Rate is utilized (see Ptb, EO Option
only, page 29).
12
Profile Loop Count
PLCt
0 to 9999, 0-continuous
**
13
Deviation Hold after
dhru
0 to 3000 units
**
Ramp Up
0=no auto hold
14
Deviation Hold after
dhrd
0 to 3000 units
**
Ramp Down
0=no auto hold
15
Profile End control
PEnd
-1=Hold at last setpoint
**
0=Abort - all outputs off
or at 0% Events off
1=Transfer to profile 1
2=Transfer to profile 2
3=Transfer to profile 3
4=Transfer to profile 4
5=Transfer to profile 5
6=Transfer to profile 6
7=Transfer to profile 7
8=Transfer to profile 8
After selecting the Profile End Control parameter value, press the SCROLL key to advance
the display to Pn. Press the UP key with Pn or any parameter code displayed to exit the
Profile Entry Mode. (Continued on next page)
DISPLAY AVAILABLE
FACTORY YOUR
STEP
DESCRIPTION
CODE
SETTINGS
SETTING SETTING