Electronic for proportional DC valves
Series PWDXXA-40X

Operation Manual

PWDXXA-40X_20 5715-677 UK.indd 26.01.17

Parker Hannifin Corporation

Hydraulics Group

Parker Hannifin Corporation

Hydraulics Group

Individual description of expert parameters

P5

dither amplitude

Adjustment of dither amplitude.
To reduce the influence of solenoid friction.

P6

dither frequency

Adjustment of dither frequency.
To match the dither signal to the valve dynamic.

P9

initial current channel A

Adjustment of the bias current for the solenoid of the valve side A.
To compensate for the solenoid initial current.

P10

initial current channel B

Adjustment of the bias current for the solenoid of the valve side B.
To compensate for the solenoid initial current.

P13

bypass gain

Adjustment of the bypass gain for the controller.
To improve the control dynamic.

P14

T-portion of PT1

Adjustment of the integral action time for the PT1-portion of the controller.
To attenuate for the P-portion.

P16

P-portion

Adjustment of the P-portion for the controller.
For the basic tuning of the controller.

P17

I-portion

Adjustment of the I-portion for the controller.
To reduce the control failure.

P18

D-portion

Adjustment of the D-portion for the controller.
To improve the control dynamic.

P19

T-portion of DT1

Adjustment of the pre-hold time for the DT1-portion of the controller.
To attenuate for the D-portion.

P20

feedback scaling

Adjustment of the scaling factor for the feedback signal.
To match the feedback signal span to the operating range.

P21

window for 

comparator function

Adjustment of the comparator window for the feedback monitoring.
To adjust the feedback monitoring range.

P23

comparator rise 

delay time

Adjustment of the comparator rise delay time.
To delay the rise threshold for the comparator function.

P24

comparator turn-off 

delay time

Adjustment of the comparator turn-off delay time.
To delay the turn-off threshold for the comparator function.

P26

window for I-gain 

activation

Adjustment of the I-portion active range in terms of the control difference.
To limit the I-portion on a certain range.

P27

I-gain window reduction

Adjustment of the I-portion outside the window in terms of the control difference.
To match the response behaviour to the I-portion.

E2

control mode

Adjustment of the operating mode for the controller.
To select the control function.

E11

type of feedback device

Adjustment of the feedback device type.
To match the feedback input to the signal device features.

E12

cable break 

detection feedback

Adjustment of the operating mode for the feedback cable break detection.
To turn on resp. off of the cable break detection for the feedback signal.

E25

MIN operating 

threshold

Adjustment of the MIN operating threshold.
To match the response sensitivity for the MIN-stroke step.

IA

nominal current 

solenoid A

Adjustment of the maximum current for the solenoid of the valve side A.
To match the solenoid output to the nominal current of the solenoid.

IB

nominal current 

solenoid B

Adjustment of the maximum current for the solenoid of the valve side B.
To match the solenoid output to the nominal current of the solenoid.

J2

Compability mode

Adjustment of the control cycle.
To adapt the cycle time to design version <20.

E81

Funktion

"Sensor supply" pin

Adjustment of the "Sensor supply" pin.
To select the function sensor supply or comparator out.

Содержание PWD Series

Страница 1: ...0X Design 20 Electronic for Proportional DC Valves Parker Hannifin Manufacturing Germany GmbH Co KG Hydraulic Controls Division Europe Gutenbergstr 38 41564 Kaarst Germany Tel 49 181 99 44 43 0 E mail...

Страница 2: ...ting is solely responsible for making the final selection of the system and components and assuring that all performance endurance maintenance safety and warning requirements of the application are me...

Страница 3: ...rtant details 8 3 1 Intended usage 8 3 2 Common instructions 8 3 3 Liability 8 3 4 Storage 8 4 Mounting Installation 9 4 1 Scope of supply 9 4 2 Mounting 9 4 3 Operation limits 9 4 4 Electrical connec...

Страница 4: ...r Hannifin Corporation Hydraulics Group 1 Introduction 1 1 Front view dimensions Position control universal Electronic module for DC valves Design series Amplifier Min Max adjustment accel decel ramps...

Страница 5: ...neces sary functions for the optimal operation of pro portional directional control valves with position sensor The most important features are digital circuit design parametrizable control as positi...

Страница 6: ...oid output off 3 8 mA solenoid output on acc NAMUR NE43 Input signal resolution 0 025 Differential input voltage max V 30 for terminals 5 and 6 against PE terminal 8 11 for terminals 5 and 6 against 0...

Страница 7: ...7 Electronic for proportional DC valves Series PWDXXA 40X Operation Manual PWDXXA 40X_20 5715 677 UK indd 26 01 17 Parker Hannifin Corporation Hydraulics Group 1 7 Signal flow diagram...

Страница 8: ...contamination atmospheric exposure and mechanical damages 2 Safety instructions Please read the operation manual before installa tion startup service repair or stocking Paying no attention may result...

Страница 9: ...y and the supplier 4 2 Mounting Compare electronics type located on the name plate with part list resp circuit diagram The module may be mounted in any direction The module has to be mounted within a...

Страница 10: ...ne frame The earth ground wire from terminal 8 as well as the cable shields have to be tied to the protective earth terminal within the control unit It is necessary to use a low ohmic potential connec...

Страница 11: ...enable function represents no safety arrangement against unwanted valve opera tion in terms of rules for accident prevention To block the valve function under all condi tions more advanced steps are...

Страница 12: ...ndi tion as breakdown information This means the presence of an evaluable failure informa tion if the input signal line is interrupted In this case the solenoid output will be switched off The output...

Страница 13: ...optional comparator output A voltage information representing the feedback signal i e the valve stroke is available from the terminals 7 and 13 Herewith a voltage span of 10 V 0 10 V means 100 0 100 f...

Страница 14: ...ain any protective or indication components i e re covery diodes or lamps otherwise function disturbances and permanent damages may occur to the electronics module Sensor input The sensor has to be wi...

Страница 15: ...40X_20 5715 677 UK indd 26 01 17 Parker Hannifin Corporation Hydraulics Group Wiring diagram of standard sensor input Parker valves Wiring diagram of sensor input 0 10 V Wiring diagram of sensor input...

Страница 16: ...DXXA 40X Operation Manual Parker Hannifin Corporation Hydraulics Group Example 1 Closed loop pressure control within a hydraulic cylinder performed utilizing a proportional pres sure con trol valve wi...

Страница 17: ...l PWDXXA 40X_20 5715 677 UK indd 26 01 17 Parker Hannifin Corporation Hydraulics Group Example 2 Closed loop position control of a hydraulic cylinder utilizing a proportional directional control valve...

Страница 18: ...alves Series PWDXXA 40X Operation Manual Parker Hannifin Corporation Hydraulics Group Example 3 Closed loop position control of a hydraulic cylinder performed via proportional directional control valv...

Страница 19: ...d entry mask the parameters can be noticed and modified Storage of complete param eter sets to floppy or hard disk is possible as well as printout or record as a text file for further docu mentation S...

Страница 20: ...butors for elec tronic components A proper function of the data communication requires in this case at least the following described cable configuration The cable has to be inserted between an unused...

Страница 21: ...ata retrieving is always possible via the function Load out of database Extended functions The user software is shared into 2 parameter ranges basic mode expert mode For normal startup the basic mode...

Страница 22: ...tronics functionality a manual pre selection of the parameters is possible After selection of the electronics type via the menu Options the parameters may be set and stored for later transmission Note...

Страница 23: ...stment of maximum stroke for valve side B at 100 command signal To match the command signal span to the valve operating range P7 MIN channel A Adjustment of stroke step for valve side A at 0 1 command...

Страница 24: ...0 P23 comparator rise delay time ms 0 10000 0 P24 comparator turn off delay time ms 0 10000 0 P26 window I portion 0 200 0 20 0 P27 reduct window I portion 0 100 0 100 0 E2 closed loop control 0 inac...

Страница 25: ...eedback monitoring To adjust the feedback monitoring range P23 comparator rise delay time Adjustment of the comparator rise delay time To delay the rise threshold for the comparator function P24 compa...

Страница 26: ...proportional P integral I and derivative D each with a user adjustable co efficient The user software provides therefore the parameters P16 P P17 I and P18 D P P16 This term provides an immediate out...

Страница 27: ...functionality of the control loop be achieved At first you should set off the control loop set parameter E2 to value 0 open loop and transmit to the electronic and cause the drive via manual control...

Страница 28: ...us items Unexplainable problems Check the setting of all parameters Improving system performance Using the parameter P17 I gain The integrator gain abbreviated I can be adjusted to reduce or eliminate...

Страница 29: ...e the best system dynamic sensors with integrated D A converter should operate with a high sampling rate Magnetostric tive transducers with digital output often have a low sampling rate because an int...

Страница 30: ...ow will be leaving which might be adjustable by parameter P26 P26 shall be adjusted in the way that the window lies near the final pressure A too low a value of P17 causes low frequency oscillations w...

Страница 31: ...t may be difficult for you to tell how good the system response is the test profile may also be generated by an up stream electronic module PZD00A 40X The test profile should start caus ing the system...

Страница 32: ...tter error reduction while the response will be longer This parameter is only effective if a window 0 is defined via P26 Eliminating a slow small amplitude oscillation in stationary condition Due to t...

Страница 33: ...troller updates the electrical output to the valve at 1000 Hz This rate is fast enough to have negligible effect in almost all hydraulic applications but it does set an absolute limit on the response...

Страница 34: ...the exact spelling case sensitivity Wrong input An unvalid character or a value outside the permitted range has been used at parameter entry Keep the entered parameters During parameter loading from t...

Страница 35: ...ls tight fit on the mounting rail tight fit of the disconnectable terminals tight fit of the terminal screws environmental temperature level supply voltage level cleanliness of the ambience Service wo...

Страница 36: ...t of a sluggish spool the valve may be flushed with clean pressure fluid Trouble shooting in a hydraulic system requires in either case a systematic approach The work may exclusively be performed by q...

Страница 37: ...port for starting up Parker hydraulic controls maintenance of Parker controls repairofallParkerrelatedhydraulicandelectrical devices assistanceinthesupplyofsparepartsworldwide direct service for mobil...

Страница 38: ......

Отзывы: