background image

12

PWDXXA-40X_20 5715-677 UK.indd 26.01.17

Electronic for proportional DC valves
Series PWDXXA-40X

Operation Manual

Parker Hannifin Corporation

Hydraulics Group

Parker Hannifin Corporation

Hydraulics Group

Wiring diagram of voltage command input +10...0...-10 V

Wiring diagram of voltage command input  +20...0...-20 mA

Wiring diagram of current input  4...12...20 mA

 

The option 4...20 mA uses the “0mA” condi-
tion as breakdown-information. This means 
the presence of an evaluable failure informa-
tion if the input signal line is interrupted. In 
this case the solenoid output will be switched 
off. The output will switched on when the input 
signal reaches a value of 3.8 mA, it switches 

off when the command falls below 3.6 mA. 
This determination follows the NAMUR-
specification NE43. If necessary, the com-
mand signal cable break detection can be 
disabled by selecting the parameter E19.

 

NAMUR is an association of users of proc-
ess control technology.

Содержание PWD Series

Страница 1: ...0X Design 20 Electronic for Proportional DC Valves Parker Hannifin Manufacturing Germany GmbH Co KG Hydraulic Controls Division Europe Gutenbergstr 38 41564 Kaarst Germany Tel 49 181 99 44 43 0 E mail...

Страница 2: ...ting is solely responsible for making the final selection of the system and components and assuring that all performance endurance maintenance safety and warning requirements of the application are me...

Страница 3: ...rtant details 8 3 1 Intended usage 8 3 2 Common instructions 8 3 3 Liability 8 3 4 Storage 8 4 Mounting Installation 9 4 1 Scope of supply 9 4 2 Mounting 9 4 3 Operation limits 9 4 4 Electrical connec...

Страница 4: ...r Hannifin Corporation Hydraulics Group 1 Introduction 1 1 Front view dimensions Position control universal Electronic module for DC valves Design series Amplifier Min Max adjustment accel decel ramps...

Страница 5: ...neces sary functions for the optimal operation of pro portional directional control valves with position sensor The most important features are digital circuit design parametrizable control as positi...

Страница 6: ...oid output off 3 8 mA solenoid output on acc NAMUR NE43 Input signal resolution 0 025 Differential input voltage max V 30 for terminals 5 and 6 against PE terminal 8 11 for terminals 5 and 6 against 0...

Страница 7: ...7 Electronic for proportional DC valves Series PWDXXA 40X Operation Manual PWDXXA 40X_20 5715 677 UK indd 26 01 17 Parker Hannifin Corporation Hydraulics Group 1 7 Signal flow diagram...

Страница 8: ...contamination atmospheric exposure and mechanical damages 2 Safety instructions Please read the operation manual before installa tion startup service repair or stocking Paying no attention may result...

Страница 9: ...y and the supplier 4 2 Mounting Compare electronics type located on the name plate with part list resp circuit diagram The module may be mounted in any direction The module has to be mounted within a...

Страница 10: ...ne frame The earth ground wire from terminal 8 as well as the cable shields have to be tied to the protective earth terminal within the control unit It is necessary to use a low ohmic potential connec...

Страница 11: ...enable function represents no safety arrangement against unwanted valve opera tion in terms of rules for accident prevention To block the valve function under all condi tions more advanced steps are...

Страница 12: ...ndi tion as breakdown information This means the presence of an evaluable failure informa tion if the input signal line is interrupted In this case the solenoid output will be switched off The output...

Страница 13: ...optional comparator output A voltage information representing the feedback signal i e the valve stroke is available from the terminals 7 and 13 Herewith a voltage span of 10 V 0 10 V means 100 0 100 f...

Страница 14: ...ain any protective or indication components i e re covery diodes or lamps otherwise function disturbances and permanent damages may occur to the electronics module Sensor input The sensor has to be wi...

Страница 15: ...40X_20 5715 677 UK indd 26 01 17 Parker Hannifin Corporation Hydraulics Group Wiring diagram of standard sensor input Parker valves Wiring diagram of sensor input 0 10 V Wiring diagram of sensor input...

Страница 16: ...DXXA 40X Operation Manual Parker Hannifin Corporation Hydraulics Group Example 1 Closed loop pressure control within a hydraulic cylinder performed utilizing a proportional pres sure con trol valve wi...

Страница 17: ...l PWDXXA 40X_20 5715 677 UK indd 26 01 17 Parker Hannifin Corporation Hydraulics Group Example 2 Closed loop position control of a hydraulic cylinder utilizing a proportional directional control valve...

Страница 18: ...alves Series PWDXXA 40X Operation Manual Parker Hannifin Corporation Hydraulics Group Example 3 Closed loop position control of a hydraulic cylinder performed via proportional directional control valv...

Страница 19: ...d entry mask the parameters can be noticed and modified Storage of complete param eter sets to floppy or hard disk is possible as well as printout or record as a text file for further docu mentation S...

Страница 20: ...butors for elec tronic components A proper function of the data communication requires in this case at least the following described cable configuration The cable has to be inserted between an unused...

Страница 21: ...ata retrieving is always possible via the function Load out of database Extended functions The user software is shared into 2 parameter ranges basic mode expert mode For normal startup the basic mode...

Страница 22: ...tronics functionality a manual pre selection of the parameters is possible After selection of the electronics type via the menu Options the parameters may be set and stored for later transmission Note...

Страница 23: ...stment of maximum stroke for valve side B at 100 command signal To match the command signal span to the valve operating range P7 MIN channel A Adjustment of stroke step for valve side A at 0 1 command...

Страница 24: ...0 P23 comparator rise delay time ms 0 10000 0 P24 comparator turn off delay time ms 0 10000 0 P26 window I portion 0 200 0 20 0 P27 reduct window I portion 0 100 0 100 0 E2 closed loop control 0 inac...

Страница 25: ...eedback monitoring To adjust the feedback monitoring range P23 comparator rise delay time Adjustment of the comparator rise delay time To delay the rise threshold for the comparator function P24 compa...

Страница 26: ...proportional P integral I and derivative D each with a user adjustable co efficient The user software provides therefore the parameters P16 P P17 I and P18 D P P16 This term provides an immediate out...

Страница 27: ...functionality of the control loop be achieved At first you should set off the control loop set parameter E2 to value 0 open loop and transmit to the electronic and cause the drive via manual control...

Страница 28: ...us items Unexplainable problems Check the setting of all parameters Improving system performance Using the parameter P17 I gain The integrator gain abbreviated I can be adjusted to reduce or eliminate...

Страница 29: ...e the best system dynamic sensors with integrated D A converter should operate with a high sampling rate Magnetostric tive transducers with digital output often have a low sampling rate because an int...

Страница 30: ...ow will be leaving which might be adjustable by parameter P26 P26 shall be adjusted in the way that the window lies near the final pressure A too low a value of P17 causes low frequency oscillations w...

Страница 31: ...t may be difficult for you to tell how good the system response is the test profile may also be generated by an up stream electronic module PZD00A 40X The test profile should start caus ing the system...

Страница 32: ...tter error reduction while the response will be longer This parameter is only effective if a window 0 is defined via P26 Eliminating a slow small amplitude oscillation in stationary condition Due to t...

Страница 33: ...troller updates the electrical output to the valve at 1000 Hz This rate is fast enough to have negligible effect in almost all hydraulic applications but it does set an absolute limit on the response...

Страница 34: ...the exact spelling case sensitivity Wrong input An unvalid character or a value outside the permitted range has been used at parameter entry Keep the entered parameters During parameter loading from t...

Страница 35: ...ls tight fit on the mounting rail tight fit of the disconnectable terminals tight fit of the terminal screws environmental temperature level supply voltage level cleanliness of the ambience Service wo...

Страница 36: ...t of a sluggish spool the valve may be flushed with clean pressure fluid Trouble shooting in a hydraulic system requires in either case a systematic approach The work may exclusively be performed by q...

Страница 37: ...port for starting up Parker hydraulic controls maintenance of Parker controls repairofallParkerrelatedhydraulicandelectrical devices assistanceinthesupplyofsparepartsworldwide direct service for mobil...

Страница 38: ......

Отзывы: