Operating Instructions
COMPAX-M / -S
Digital inputs and outputs
152
If MZ travel is interrupted by the synchronous stop, then O3 "Machine zero
approached" is not output.
P219 = xx000000=0: COMPAX-M does not evaluate the additional emergency
stop input.
(Additional emergency stop input: X9/5-X9/6 (front plate);
COMPAX-M only)
P219 = xx000111=7: Emergency stop with P10 as relative ramp time, then switch
off, message E56, display E56, output O1 = 0, ready contact
removed.
Also effective in programming mode!
Note for MZ travel:
Additional
assignment of
P219: