Operating Instructions
COMPAX-M / -S
Digital inputs and outputs
146
Logical inputs *
I1...I8
Field bus I17...I24
Logical inputs *
I9...I16
Field bus I25...I32
≥≥≥≥
1
="0"
P222
="1"
="0"
P221
="1"
COMPAX –
control functions
Depends on COMPAX
device variants (for
P222=”0” corresponds to
arrangement of inputsIE9
to I16)
COMPAX - control
functions
(for P221=”0”
corresponds to
arrangement of inputs I1
to I8)
SHIFT, Hand+, Hand-,
Quit, Start, Stop,
approach Mn, approach
RN, Tech RN
logical I1...I8
logical I9...I16
logical
I9...I16
COMPAX–command
I41...I48
(OTA41...OTA48)
Structural diagram: Access to
COMPAX control functions via
inputs
*
The logic inputs I1 ... I16 are,
excluding COMPAX 1000SL, also
the physical inputs I1 ...I16 on
connectors X8 and X10.
With COMPAX 1000SL, the 8
physical inputs on connector X19
are allocated (via parameters P156
... P158) to 8 logic inputs from the
range I1 ... I16 (see Page 140)
Remarks regarding the structural diagram
♦
The control functions corresponding to I1.. I8
cannot
be activated via OT
O33...OT O40.
♦
The control functions corresponding to I9...I16 can be activated simultaneously
via the physical inputs and via OT O41...OT O48.
♦
The enable input I12 (in COMPAX 1000SL, COMPAX XX70 and COMPAX XX30)
must also be activated when allocated to the fieldbus (via P222).
Interrogation of inputs in the COMPAX program (IF I ..)
All inputs can be interrogated independently of parameters P221 and P222 in the
COMPAX program with IF I... .
The virtual inputs I33...I48 in the COMPAX program can also be set via the
commands OT O33...OT O48.
COMPAX–command
I33...I40
(OTA33...OTA40)
COMPAX–command
I41...I48
(OTA41...OTA48)
Logical inputs *
I1...I8
Field bus I17...I24
Logical inputs *
I9...I16
Field bus I25...I32
COMPAX – program
Interrogation of inputs with
IF I1=
To
IF I48=
Regardless of parameters
P221 and P222
With P233=48 (or P234=48), virtual inputs I48 – I25 are written to the optimization
display status S13 (S14). Meaning: I25 = bit 0 ... I48 = bit 23.