Page 8
Installation
For European installations and countries with EMC legislation refer to the 890 Engineering Reference
Manual, Appendix C.
Mounting Dimensions
With any tall unit such as the AC890PX drive, it is advisable to
secure the top to prevent it tipping over.
During operation it must stand vertically on a solid, flat,
horizontal, normally cool, non-flammable surface.
The bottom wire entry version of the drive will sit on a plinth
(allowing the cables to be fed through the bottom of the drive).
In this case, also secure the drive to the plinth.
Refer to Chapter 3: Installation Drawings in the Engineering
Reference manual for more information.
Air Flow
It is important that the top vent is properly fitted to assure that
the exhaust air is not recirculated.
It is important that air heated by other items should not affect
the inlet temperature to the drive’s fans.
Maximum Weight kg/lbs
Cabinet
Height
Cabinet
Width
Cabinet
Depth
Vent Hood
Height
132kW
600lbs (272kg)
200kW
600lbs (272kg)
315kW
732lbs (333kg)
400kW
790lbs (360kg)
2024mm
(79.7")
500mm
(19.7")
620mm
(24.4")
280mm
(11.0")
Environmental Conditions
Operating ambient temperature
0°C to 40°C (32°F to 104°F)
Enclosure rating
IP4X – UL(cUL) Enclosed Type 1
Atmosphere
Dust
free,
non
flammable, non-corrosive, <85% humidity,
non-condensing
2/3
OUTLET AIR
1000 CFM 1700 CMH
Total flow at full load
INLET AIR
1/3
OUTLET AIR
100cm
minimum
air
clearance
Содержание AC890PX Series
Страница 6: ...Page 6 Overview AC890PX top wire entry...
Страница 7: ...Page 7 AC890PX bottom wire entry...
Страница 12: ...Page 12 Wiring Diagram Bottom Wire Entry...
Страница 23: ...Page 23...
Страница 24: ...Page 24 Appendix C Electrical Ratings...
Страница 25: ...Page 25...
Страница 26: ...Page 26...