Page
17
Quick Setup Parameters
The following is a list of the Quick Setup parameters you must check before starting the drive. Set only
the ones marked with “x” in the table below, under the intended mode of operation.
V/Hz SV Vector PMAC
Control Mode
Select the intended operating mode
x
x
x
x
Max Speed
Motor RPM at full process speed
x
x
x
x
V/F shape
Usually Linear. Choose fan curve only for fans
x
Motor Current
Motor full load current from motor nameplate
x
x
x
Motor Base Freq Motor nameplate frequency
x
x
x
Motor Voltage
Motor nameplate voltage
x
x
x
Nameplate RPM Motor nameplate RPM
x
x
x
Motor Poles
See Note
x
x
Pulse Enc Volts
Set between 10-20V to match encoder
x
Encoder Lines
Pulses per Revolution of encoder
x
Encoder Invert
Changes polarity of encoder feedback
x
Autotune Enable Drive will Autotune if started
x
x
Mag Current
Enter the No-Load Amps from the motor nameplate
x* x*
•
if performing a Stationary Autotune.
NOTE
Some of the parameters are product code dependent, that is, they are different for each
frame size and power rating. For example, the unit will be set for either 50Hz or 60Hz
operation:
Motor Poles for 60Hz 2 poles = 3600 rpm, 4 poles = 1800 rpm, 6 poles = 1200 rpm
Motor Poles for 50Hz 2 poles = 3000 rpm, 4 poles = 1500 rpm, 6 poles = 1000 rpm
Содержание AC890PX Series
Страница 6: ...Page 6 Overview AC890PX top wire entry...
Страница 7: ...Page 7 AC890PX bottom wire entry...
Страница 12: ...Page 12 Wiring Diagram Bottom Wire Entry...
Страница 23: ...Page 23...
Страница 24: ...Page 24 Appendix C Electrical Ratings...
Страница 25: ...Page 25...
Страница 26: ...Page 26...