Page
11
Components : Bottom Wire Entry
A
Isolator
B
Control Module/Control
Terminals
C
Auxiliary Transformer
Set the transformer taps -
see page 13.
D
Motor/Output Connections
E
Protective Earth/Ground
F
Internal Brake Resistor Thermal
Overload Protection
G
User Blower Motor Thermal
Overload Protection
H
Auxiliary Supply Protection -
Circuit Breaker (primary)
I
Auxiliary Supply Protection -
Semiconductor Fuse
(secondary)
J
External Brake Resistor
Terminal Block
K
3-Phase Connections
Permanent Earthing
Each unit must be
permanently earthed
according to EN 61800-5. For permanent earthing,
EN 61800-5 states that:
A cross-section conductor of at least 10mm² copper or 16mm
2
aluminium is required.
Conductors must be sized in accordance with Local Wiring Regulations which always take
precedence.
As a guide, refer to the Input Current for the drive given in the Electrical Ratings tables.