GPIO:
Configuration Example:
AI3
±10 V Variable Input (from potentiometer)
AI4
0-10 V Variable Input (from potentiometer)
AO4
0-10 V Variable Output (to voltmeter)
DX11
+24 V Output (to relay coil)
Terminal Block Wire Range
The control board terminal wire range is as follows:
Terminal Wire Range
Min
Max
0.2 mm
2
(24 AWG)
1.0 mm
2
(18 AWG)
Wire sizes for Europe should be chosen with respect to the operating conditions and your local National
Electrical Safety Installation Requirements. Local wiring regulations always take precedence.
Recommended Wire & Ferrule Sizes
The following wire sizes and ferrules are recommended for use with the control board terminal blocks:
Wire Type
Maximum
Wire Size
Ferrule Details
Bare Wire / Ferrule
Length
Stranded
1x 1.0 mm
2
(1x 18 AWG)
None Fitted
5 mm
(0.20”)
2x 0.5 mm
2
(2x 21 AWG)
None Fitted
Stranded
1x 0.75 mm
2
(1x 19 AWG)
White Collar,
1.5 mm OD
6 mm
(0.24”)
1x 0.5 mm
2
(1x 21AWG)
Orange Collar, 1.3 mm
OD
Terminal Block Tightening Torque
The control board terminals should be screwed to a maximum torque as specified below:
Screw Head
Terminal Tightening Torque
M2, Flat
0.19 Nm
(1.7 Lb-in)
V
+
24V
Содержание AC20F Series
Страница 144: ...MSG11 5715 743 EN AC20F Series Hardware Installation Manual 144 148 MSG11 5715 743 EN 24 04 2023 Frame 3...
Страница 145: ...MSG11 5715 743 EN AC20F Series Hardware Installation Manual MSG11 5715 743 EN 24 04 2023 145 148 Frame 4 Frame 5...
Страница 146: ...MSG11 5715 743 EN AC20F Series Hardware Installation Manual 146 148 MSG11 5715 743 EN 24 04 2023 Frame 6 Frames 7 8...
Страница 147: ...MSG11 5715 743 EN AC20F Series Hardware Installation Manual MSG11 5715 743 EN 24 04 2023 147 148 Frame 9 Frame 10...
Страница 148: ...MSG11 5715 743 EN AC20F Series Hardware Installation Manual 148 148 MSG11 5715 743 EN 24 04 2023...