MSG11-5715-743/EN: AC20F Series - Hardware Installation Manual
MSG11-5715-743/EN 24.04.2023
101 (148)
Application ‘2’: Auto / Manual
Two Run inputs and two Setpoint inputs are provided. The Auto/Manual switch selects which pair of inputs
is active.
The Application is sometimes referred to as Local/Remote.
Configuration Setup:
RL1A
110-230 VAC (or 24 VDC) voltage supply
RL1B
Healthy:
Relay output (to lamp)
TH1
Motor Thermistor ‘+’ connection
TH2
Motor Thermistor ‘-’ connection
AI1
‘Manual’ Remote Setpoint (%):
0-10 V variable input (from potentiometer)
AI2
‘Auto’ Remote Setpoint (%):
4-20 mA variable input (from current source)
AO1
Speed Demand (%):
0-10 V variable output (to voltmeter)
AO2
Value = 100%:
0-10 V variable output (+10 V fixed reference voltage)
DX1
‘Manual’ Run:
24 V digital input
DX2
‘Auto’ Run:
24 V digital input
DX3
Auto / Manual Select:
24 V digital input
DI4
Remote Reverse:
24 V digital input
DI5
Not Coast Stop:
24 V digital input
STO
STO
DISABLED
(drive operational)
V
↑
V
S
Содержание AC20F Series
Страница 144: ...MSG11 5715 743 EN AC20F Series Hardware Installation Manual 144 148 MSG11 5715 743 EN 24 04 2023 Frame 3...
Страница 145: ...MSG11 5715 743 EN AC20F Series Hardware Installation Manual MSG11 5715 743 EN 24 04 2023 145 148 Frame 4 Frame 5...
Страница 146: ...MSG11 5715 743 EN AC20F Series Hardware Installation Manual 146 148 MSG11 5715 743 EN 24 04 2023 Frame 6 Frames 7 8...
Страница 147: ...MSG11 5715 743 EN AC20F Series Hardware Installation Manual MSG11 5715 743 EN 24 04 2023 147 148 Frame 9 Frame 10...
Страница 148: ...MSG11 5715 743 EN AC20F Series Hardware Installation Manual 148 148 MSG11 5715 743 EN 24 04 2023...