MSG11-5715-743/EN: AC20F Series - Hardware Installation Manual
36 (148)
MSG11-5715-743/EN 24.04.2023
Frames 7
– 10:
To access the
AC Line Y-Cap
&
VDR
links:
1. Remove the Lower Terminal cover.
2. Adjust the link positions. Removing the link completely is the same as placing the links in the
‘disconnected’ (pin 2 – 4) position.
To access the
DC Link Y-Cap
link:
1. Remove the Lower Terminal cover.
2. Carefully remove the Upper Terminal cover, disconnecting the onboard keypad cable from the top
of the control board.
3. Adjust the link position of CN5. Removing the link completely is the same as placing the link in the
‘disconnected’ (pin 2 – 4) position.
J1
‘EMC’ AC
Line Y-Cap &
Y1
’VAR’
VDR Links
CN5
DC Link
Y-Cap Link