Easy Start Guide

Page 5

This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright

The Inverter

Drive Supermarket and must not be reproduced or altered without prior written permission.

©

4. Parameters - overview

Parameter

Description

How to set

F111

Maximum Frequency (Hz)

Maximum frequency for the Inverter. Default is

which suits most applications.

50

F112

Minimum Frequency (Hz)

Minimum frequency for the Inverter. Default is

which suits most applications.

0.5

F114

First Acceleration Time (s)

Default is

seconds; increase or decrease if faster or slower acceleration is required.

5

F115

First Deceleration Time (s)

Default is

seconds; increase or decrease if faster or slower deceleration is required.

5

F137

Torque Compensation Mode

Default is

;  can be set to 1 for centrifugal fan and pump applications.

auto

F153

Carrier Frequency

Setting is rating dependent. Only change if required; default will suit most applications.

F200

Start Command Source

Default is

for te MODBUS (any input source).

4

F201

Stop Command Source

Default is

for te MODBUS (any input source).

4

F203

(desired motor speed in Hz)

Frequency Command Source

F113 is adjusted by the keypad and stored. No need to change either F113 or F203.

Default is 'Memory' which is set by parameter F113;

F209

Stopping Mode

Default is , ramped stop. Change to 1 for coast stop; this may suit some fan loads.

0

F220

Frequency Memory

Default is ; can be set to 1 to store the keypad setpoint (F113) during power down.

0

F228

Application Selection

Defaults below are based on F228 = 0

Default is ; will suit most applications. 5 different application Macros available.

0

F801

Rated Motor Power (kW)

Rated kW of the motor. Set to match the motor nameplate eg.

(2.2kW)

2200

F802

Rated Motor Voltage (V)

Rated Voltage of the motor. Set to match the motor nameplate eg

V

230

F803

Rated Motor Current (A)

Rated current of the motor. Set to match the motor nameplate eg

A

2.4

F805

Base Motor rpm

Once this is set, read-only parameter F804 (number of motor poles) will be recalculated.

Rated rpm of the motor. Set to match the motor nameplate eg

rpm (min-1)

1460

F810

Motor rated Freq

Rated frequency of the motor. Default is

Hz; change to suit the motor.

50

Parameters are typically referred to by code or
number (eg. F803 = Rated Motor Current) with
a description available in the manual.

The Inverter contains a number of settings
which can be changed to tailor it for use in a
wide range of applications. These settings are
known as parameters.

The parameters contain critical information
essential to the correct operation of the
Inverter. Therefore, they should at least be
checked by the user before the Inverter is
operated for the first time.
The parameters listed in section 5 are intended
to provide a starting point to allow for basic
operation of the AC10 Inverter.

5. Parameters to set before use

See section 6 to learn how to set a parameter value.

Set the following parameters to allow the AC10
to control a motor with Run, Stop and Speed
Control from the keypad.

If any of the parameters have been changed
previously, follow the procedure in section 14
to reset the Inverter to Factory Defaults.

5.1 Parameters to check and values to set

Parker AC10 Series Inverter (to 22kW)

Содержание AC10 series

Страница 1: ...a safety device All safety considerations including but not limited to Emergency Stop provision should be assessed separately and are outside the scope of this guide Parker AC10 Frequency Inverter to...

Страница 2: ...nd configure a Potentiometer for remote speed control Contents Parameters Overview Parameters to set before use How to connect and configure a Run Stop switch with Forward Reverse selection Power and...

Страница 3: ...tor phases determines the initial direction the motor turns Notes Important Use screened or armoured cable between the Inverter and Motor and ensure it is grounded as shown The supply must match the I...

Страница 4: ...is not important They should be connected to the terminals marked L1 R L2 S and L3 T as shown In some cases these terminals may be marked L1 L2 and L3 only Notes The order of the three motor phases d...

Страница 5: ...hanging from Delta to allow the motor to be changed back in future For safety purposes Star shown opposite is the default configuration for small motors usually to 3kW and is sometimes known as two at...

Страница 6: ...power down 0 F228 Application Selection Defaults below are based on F228 0 Default is will suit most applications 5 different application Macros available 0 F801 Rated Motor Power kW Rated kW of the...

Страница 7: ...roup mode the DGT digit lamp is not illuminated 6 2 Select the required parameter group Use the up and down keys to select parameter group F800 6 3 Select the required parameter Press the 0 stop key t...

Страница 8: ...used to cycle through other values such as motor rpm current A and voltage U Parker AC10 Series Inverter to 22kW 7 1 Select the speed reference Press the M key repeatedly until the speed reference is...

Страница 9: ...Motor Power kW Rated kW of the motor Set to match the motor nameplate eg 2 2kW 2200 F802 Rated Motor Voltage V Rated Voltage of the motor Set to match the motor nameplate eg V 230 F803 Rated Motor Cu...

Страница 10: ...rated from 2kOhm to 5kOhm can be used eg 4 7kOhm The default output frequency at 0V is the minimum frequency of the Inverter To change this edit Parameter F112 The default output frequency at 10V is...

Страница 11: ...on opposite When a connection is made between terminals 24V and DI3 the motor will run forward When terminals 24V and DI4 are connected the motor will run in reverse The selected direction of rotation...

Страница 12: ...15 set to to select Run Fwd 15 F319 DI4 terminal function setting Default is 16 set to to select Run Rev 16 11 1 Parameters to change for remote Run Stop Two suitable 2 position NO Normally Open swit...

Страница 13: ...rse Select Open Forward Closed Reverse 16 12 1 Parameters to change for remote 3 wire control Note that the Forward Reverse switch can be used to set the direction when the motor is stopped or running...

Страница 14: ...or manual issued by the manufacturer for details 13 2 Connecting the Resistor The braking resistor may get hot during operation Ensure that it is suitably mounted so any heat generated will not affec...

Страница 15: ...0 F800 etc Use the up and down keys to select parameter group F100 14 2 Select parameter group 1 Note In parameter group mode the DGT digit lamp is not illuminated Use the up and down keys to select p...

Отзывы: