Function
Code
Function Definition
Setting Range
Mfr’s
Value
Change
F700
Selection of terminal
free stop mode
0: Immediate free stop (coast
stop);
1: Delayed free stop (coast stop)
0
√
F701
Delay time for free
stop (coast stop)
and programmable
terminal action
0.0-60.0s
0.0
√
F702
Fan control mode
0: Controlled by temperature
1: Run when inverter is powered
on
2: Controlled by running status
2
√
F703
Reserved
F704
Inverter Overload pre-
alarm Setpoint (%)
50~100
80
X
F705
Motor Overload pre-
alarm Setpoint (%)
50~100
80
X
F706
Inverter Overloading
Setpoint (%)
120-190
150
X
F707
Motor Overloading
Setpoint (%)
20-100
100
X
F708
Trip 1 Type (Newest)
Setting range:
2: Over current (OC)
3: Over voltage (OE)
4: Input phase loss (PF1)
5: Inverter overload (OL1)
6: Under voltage (LU)
7: Overheat (OH)
8: Motor overload (OL2)
11: External malfunction (ESP)
12: Current fault before running
(Err3)
13. Studying parameters without
motor (Err2)
15: Current sampling fault (Err4)
16: Over current 1 (OC1)
17: Output phase loss (PF0)
18: Analog disconnected (Aerr)
23: PID parameters set wrong (Err5)
45: Communication Timeout (CE)
46: Flycatching fault (FL)
49: Watchdog fault (Err6)
67: Overcurrent (OC2)
D
F709
Trip 2 Type
D
F710
Trip 3 Type
D
Parameter List and Default Settings
10-14
Содержание AC10 series
Страница 13: ...Dimensions 2 8 This page intentionally left blank...
Страница 15: ...Connections 2 10...
Страница 19: ...Panel Display IP20 Units 3 4 Items and Remarks Displayed on the Panel...
Страница 23: ...Menu Organization IP66 Units 3 8 Items and Remarks Displayed on the Panel...
Страница 33: ...The Default Applications 8 2 Application 1 Basic Speed Control...
Страница 34: ...8 3 The Default Applications Application 2 Auto Manual Control...
Страница 35: ...The Default Applications 8 4 Application 3 Preset Speeds...
Страница 36: ...8 5 The Default Applications Application 4 Raise Lower Trim...
Страница 37: ...The Default Applications 8 6 Application 5 PID...