Function
Code
Function Definition
Setting Range
Mfr’s Value Change
F500 -
F580
Multi-Stage speed control
definition table, refer to
product manual
N/A
N/A
X
Function
Code
Function Definition
Setting Range
Mfr’s Value Change
F600
DC Braking Function
Selection
0: Disabled;
1: Braking before
starting;
2: Braking during
stopping;
3: Braking during
starting and
stopping
0
X
F601
Initial Frequency for DC
Braking
0.20-50.00
1.00
√
F602
DC Braking level before
Starting (V/A)
0-100
10
√
F603
DC Braking level During Stop
(V/A)
0-100
10
√
F604
Braking Lasting Time Before
Starting (S)
0.00-30.00
0.50
√
F605
Braking Lasting Time During
Stopping (S)
0.00-30.00
0.50
√
F606
Reserved
F607
Stall Adjustment Function
0: Disabled;
1: Enabled
2: Reserved
3: Voltage current
control
4: Voltage control
5: Current control
0
√
Parameter List and Default Settings
10-12
Содержание AC10 series
Страница 13: ...Dimensions 2 8 This page intentionally left blank...
Страница 15: ...Connections 2 10...
Страница 19: ...Panel Display IP20 Units 3 4 Items and Remarks Displayed on the Panel...
Страница 23: ...Menu Organization IP66 Units 3 8 Items and Remarks Displayed on the Panel...
Страница 33: ...The Default Applications 8 2 Application 1 Basic Speed Control...
Страница 34: ...8 3 The Default Applications Application 2 Auto Manual Control...
Страница 35: ...The Default Applications 8 4 Application 3 Preset Speeds...
Страница 36: ...8 5 The Default Applications Application 4 Raise Lower Trim...
Страница 37: ...The Default Applications 8 6 Application 5 PID...