Function
Code
Function Definition
Setting Range
Mfr’s Value Change
F200
Source of start
command
0: Keypad command;
1: Terminal command;
2: Terminal;
3: MODBUS;
4: T
MODBUS
4
X
F201
Source of stop
command
0: Keypad command;
1: Terminal command;
2: Terminal;
3: MODBUS;
4: T
MODBUS
4
X
F202
Mode of direction
setting
0: Forward run locking;
1: Reverse run locking;
2: Terminal setting
3: Keypad
0
X
F203
Main frequency source
(X)
0: Digital setting memory;
1: External analog AI1;
2: External analog AI2;
3: Reserved;
4: Stage speed control;
5: No memory by digital
setting;
6: Reserved;;
7: Reserved;
8: Reserved;
9: PID output;
10: MODBUS
0
X
F204
Secondary frequency
source (Y)
0: Digital setting memory;
1: External analog AI1;
2: External analog AI2;
3: Reserved;
4: Stage speed control;
5: PID adjusting;
6: Reserved;
0
X
F205
Reference for
selecting secondary
frequency source (Y)
range
0: Relative to max freq;
1: Relative to main freq (X)
0
X
F206
Secondary frequency
(Y) range
0-100%
100
X
Parameter List and Default Settings
10-4
Содержание AC10 series
Страница 13: ...Dimensions 2 8 This page intentionally left blank...
Страница 15: ...Connections 2 10...
Страница 19: ...Panel Display IP20 Units 3 4 Items and Remarks Displayed on the Panel...
Страница 23: ...Menu Organization IP66 Units 3 8 Items and Remarks Displayed on the Panel...
Страница 33: ...The Default Applications 8 2 Application 1 Basic Speed Control...
Страница 34: ...8 3 The Default Applications Application 2 Auto Manual Control...
Страница 35: ...The Default Applications 8 4 Application 3 Preset Speeds...
Страница 36: ...8 5 The Default Applications Application 4 Raise Lower Trim...
Страница 37: ...The Default Applications 8 6 Application 5 PID...