6-28
Programming Your Application
650S AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
RUN STOP MODE
RAMPED : The motor speed is reduced to zero at a rate set by DECEL
TIME (
P
5). A 2 second DC pulse is applied at end of ramp
COAST : The motor is allowed to freewheel to a standstill
DC INJECTION : On a stop command, the motor volts are rapidly
reduced at constant frequency to deflux the motor. A low frequency
braking current is then applied until the motor speed is almost zero. This
is followed by a timed DC pulse to hold the motor shaft.
0=RAMPED
1=COAST
2=DC INJECTION
0
PASSWORD
A password may be set to prohibit unauthorised adjustment of
parameters. When
P
99 is set to non-zero you will be required to match
this value before parameters can be adjusted
0000 – FFFF
0000
APP Menu
Parameters visible when Application 3 is selected in parameter P1
PRESET 0
A user-adjustable speed preset, set by potentiometer
-100.00 to 100.00
-
PRESET 1
A user-adjustable speed preset
-100.00 to 100.00
20.00
PRESET 2
A user-adjustable speed preset
-100.00 to 100.00
50.00
PRESET 3
A user-adjustable speed preset
-100.00 to 100.00
100.00
PRESET 4
A user-adjustable speed preset
-100.00 to 100.00
-10.00
PRESET 5
A user-adjustable speed preset
-100.00 to 100.00
-20.00
PRESET 6
A user-adjustable speed preset
-100.00 to 100.00
-50.00
PRESET 7
A user-adjustable speed preset
-100.00 to 100.00
-100.00
Parameters visible when Application 4 is selected in parameter
P
1
R/L RAMP TIME
The time taken to ramp the Raise/Lower output from 0.00% to 100.00%
of its value
0.0 to 600.0s
10.0s
R/L MAX VALUE
The maximum value for the ramp output
-100.00 to 100.00% 100.00%
R/L MIN VALUE
The minimum value for the ramp output
-100.00 to 100.00% 0.00%
R/L RESET VALUE
The value the output is set to when Reset is TRUE, when DIN4 (terminal
10) is 24V in Application 4
-100.00 to 100.00% 0.00%
Parameters visible when Application 5 is selected in parameter
P
1
PI P GAIN
The PI proportional gain
0.00 to 100.00
0.10
PI I GAIN
The PI integral gain
0.00 to 100.00
1.00
PID D GAIN
The PID derivative gain
0.00 to 100.00
0.00
Содержание 650S Series
Страница 1: ...650S 650S P P Pr r ro o od d du u uc c ct t t M M Ma a an n nu u ua a al l l HA500924U001 S E R I E S ...
Страница 9: ...Cont 8 ...
Страница 13: ...1 4 Getting Started 650S AC Drive ...
Страница 39: ...4 8 Operating the Drive 650S AC Drive ...
Страница 101: ...8 4 Routine Maintenance and Repair 650S AC Drive ...
Страница 127: ...10 10 Certification for the Drive 650S AC Drive ...
Страница 128: ...Serial Communications 11 1 650S AC Drive Chapter 11 Serial Communications Connection to the P3 Port 11 2 ...