6-8
Programming Your Application
650S AC Drive
MMI Parameters Table
Display
Parameter
Description
Range
Default
DOUT 1 SOURCE
F
NONE : Relay is open
Relay is closed when:
HEALTH : the Run signal is not present, or no trip is active
TRIPPED : a trip is present
RUNNING : the motor is running
AT ZERO : the output frequency is below 1% of MAX SPEED (
P
2)
AT SPEED : the output frequency is at or near Setpoint and within ±1%
of MAX SPEED, set by (
P
2)
.
For example: if MAX SPEED = 50Hz and
Setpoint = 30Hz, then 1% of MAX SPEED = 0.5Hz. So AT LOAD is True
between 30 ±0.5Hz.
AT LOAD : the magnitude of the output torque is greater than or equal
to the torque level set in
ST
42
0 : NONE
1 : HEALTH
2 : TRIPPED
3 : RUNNING
4 : AT ZERO
5 : AT SPEED
6 : AT LOAD
0 : NONE
DOUT 2 SOURCE
Refer to
Configuring
Terminals 9 &
10 (Digital
Input/Output)
,
page 6-30
F
0 : NONE
1 : HEALTH
2 : TRIPPED
3 : RUNNING
4 : AT ZERO
5 : AT SPEED
6 : AT LOAD
0 : NONE
RELAY SOURCE
F
0 : NONE
1 : HEALTH
2 : TRIPPED
3 : RUNNING
4 : AT ZERO
5 : AT SPEED
6 : AT LOAD
1 :
HEALTH
AOUT 1 SOURCE
F
0 : NONE
1 : DEMAND
2 : CURRENT
3 : PID ERROR
4 : RAISE/LOWER
1 :
DEMAND
Содержание 650S Series
Страница 1: ...650S 650S P P Pr r ro o od d du u uc c ct t t M M Ma a an n nu u ua a al l l HA500924U001 S E R I E S ...
Страница 9: ...Cont 8 ...
Страница 13: ...1 4 Getting Started 650S AC Drive ...
Страница 39: ...4 8 Operating the Drive 650S AC Drive ...
Страница 101: ...8 4 Routine Maintenance and Repair 650S AC Drive ...
Страница 127: ...10 10 Certification for the Drive 650S AC Drive ...
Страница 128: ...Serial Communications 11 1 650S AC Drive Chapter 11 Serial Communications Connection to the P3 Port 11 2 ...