9-30
Function Parameters
AC10 Inverter
F502 Selection of number of cycles of
Auto-circulation Speed Control
Setting range: 0
~
9999
(when the value is set to 0, the
inverter will carry out infinite
circulating)
Mfr’s value: 0
F503 Status After Auto-circulation
Running Finished.
Setting range:
0: Stop
1: Keep running at last-stage speed
Mfr’s value: 0
If running mode is auto-circulation speed control (F203=4 and F500=2), please set the related
parameters by F501~F503.
The inverter runs at the preset stage speed one by one under the auto-circulation speed control
is called as cycle.
If F502=0,
inverter will run at infinite auto circulation, which will be stopped by “stop” signal.
If F502>0, inverter will run at auto circulation conditionally. When auto circulation of the preset
cycles is finished continuously (set by F502), inverter will finish auto-circulation running
conditionally. When inverter keeps running and the preset cycles is not finished, if inverter
receives “stop command”, inverter will stop. If inverter receives “run command” again, inverter will
automatically circulate by the setting time of F502.
If F503=0, then inverter will stop after auto circulation is finished. If F503=1, then inverter will
run at the speed of the last-stage after auto-circulation is finished as follows:
e.g., F501=3, then inverter will run at auto circulation of 3-stage speed;
F502=100, then inverter will run 100 cycles of auto circulation;
F503=1, inverter will run at the speed of the last stage after the auto-circulation running is
finished.
Figure 9-10 Auto-circulating Running
The inverter can be stopped by pressing “O” or sending “O” signal through terminal during
auto-circulation running.
F504 Frequency setting for stage 1 speed (Hz)
Setting range:
F112
~
F111
Mfr’s value: 5.00
F505 Frequency setting for stage 2 speed (Hz)
Mfr’s value: 10.00
F506 Frequency setting for stage 3 speed (Hz)
Mfr’s value: 15.00
F507 Frequency setting for stage 4 speed (Hz)
Mfr’s value: 20.00
F508 Frequency setting for stage 5 speed (Hz)
Mfr’s value: 25.00
F509 Frequency setting for stage 6 speed (Hz)
Mfr’s value: 30.00
F510 Frequency setting for stage 7 speed (Hz)
Mfr’s value: 35.00
F511 Frequency setting for stage 8 speed (Hz)
Mfr’s value: 40.00
F512 Frequency setting for stage 9 speed (Hz)
Mfr’s value: 5.00
F513 Frequency setting for stage 10 speed (Hz)
Mfr’s value: 10.00
F514 Frequency setting for stage 11 speed (Hz)
Mfr’s value: 15.00
F515 Frequency setting for stage 12 speed (Hz)
Mfr’s value: 20.00
Start auto
circulating
running
Stage-1
speed
Stage-2
speed
Stage-3
speed
After circulating
100 times
Keep running at
Stage-3 speed