background image

9-8

 Function Parameters

 

AC10 Inverter 

 

F152 Output voltage corresponding 

to turnover frequency 

Setting range: 0

100 

Mfr’s value: 100 

This function can meet the needs of some special loads, for example, when the frequency 

outputs 300Hz and corresponding voltage outputs 200V (supposed voltage of inverter power 

supply is 400V), turnover frequency F118 should be set to 300Hz and F152 is set to

200÷400

×100=50. And F152 should be equal to 50. 
Please pay attention to nameplate parameters of motor. If the working voltage is higher than 

rated voltage or the frequency is higher than rated frequency, motor would be damaged. 
 
 
 
Carrier-wave frequency of inverter is adjusted by setting this code function. Adjusting 

carrier-wave may reduce motor noise, avoid point of resonance of mechanical system, 

decrease leakage current of wire to earth and the interference of inverter. 
When carrier-wave frequency is low, although carrier-wave noise from motor will increase, the 

current leaked to the earth will decrease. The wastage of motor and the temperature of motor 

will increase, but the temperature of inverter will decrease. 
When carrier-wave frequency is high, the situations are opposite, and the interference will raise. 
When output frequency of inverter is adjusted to high frequency, the setting value of 

carrier-wave should be increased. Performance is influenced by adjusting carrier-wave 

frequency as below table: 

Carrier-wave frequency 

Low            →        High   

Motor noise 

Loud          →        Low   

Waveform of output current  Bad            →        Good   

Motor temperature 

High          →        Low 

Inverter temperature 

Low          →        High 

Leakage current 

Low          →        High 

Interference   

Low          →        High 

 

F154 Automatic voltage 

rectification 

Setting range: 0: Invalid 1: Valid   

2:Invalid during deceleration process 

Mfr’s value: 0 

 
This function is enabled to keep output voltage constant automatically in the case of fluctuation 

of input voltage, but the deceleration time will be affected by internal PI adjustor. If deceleration 

time is forbidden being changed, please select F154=2.   

F155    Digital secondary frequency setting 

Setting range: 

0

F111 

Mfr’s value: 0 

F156    Digital secondary frequency polarity setting 

Setting range: 

0 or 1 

Mfr’s value: 0 

F157    Reading secondary frequency   

 

 

F158 Reading secondary frequency polarity 

 

 

Under combined speed control mode, when secondary frequency source is digital setting memory 

(F204=0), F155 and F156 are considered as initial set values of secondary frequency and polarity 

(direction).   
In the mode of combined speed control, F157 and F158 are used for reading the value and direction 

of secondary frequency.   
For example, when F203=1, F204=0. F207=1, the given analog frequency is 15Hz, inverter is 

required to run to 20Hz. In case of this requirement, user can push “UP” button to raise the frequency 

from 15Hz to 20Hz. User can also set F155=5Hz and F160=0 (0 means forward, 1 means reverse). In 

this way, inverter can be run to 20Hz directly. 
 
 

F153      Carrier frequency setting 

Setting range:    subject 

to inverter model 

Mfr’s value: subject to 

inverter model   

www.comoso.com

Содержание 10G-11-0015 Series

Страница 1: ...aerospace climate control climate control electromechanical filtration filtration fluid gas handling fluid gas handling hydraulics hydraulics pneumatics pneumatics process control process control seal...

Страница 2: ...www comoso com...

Страница 3: ...nifin Ltd Although every effort has been taken to ensure the accuracy of this document it may be necessary without notice to make amendments or correct omissions Parker SSD Drives cannot accept respon...

Страница 4: ...ance endurance maintenance safety and warning requirements of the application are met The user must analyze all aspects of the application follow applicable industry standards and follow the informati...

Страница 5: ...from the equipment INSTALLATION DETAILS Model Number see product label Where installed for your own information Unit used as a refer to Certification for the Inverter Component Relevant Apparatus Uni...

Страница 6: ...sconnecting the drive from the circuit being tested Whilst ensuring ventilation is sufficient provide guarding and or additional safety systems to prevent injury or damage to equipment When replacing...

Страница 7: ...el Display 6 3 Chapter 7 Installation Connection 7 1 7 1 Installation 7 1 7 2 Connection 7 3 7 3 Measurement of Main Circuit Voltages Currents and Powers 7 5 7 4 Functions of Control Terminals 7 7 7 5...

Страница 8: ...unning and stop using the keypad panel 8 5 8 3 2 Setting the frequency using the keypad panel and starting forward and reverse running and stopping inverter through control terminals 8 6 8 3 3 Operati...

Страница 9: ...face 12 8 12 8 1 Interface instruction 12 8 12 8 2 Structure of Field Bus 12 8 12 9 Grounding and Terminal 12 8 12 9 1 Examples 12 9 Chapter 13 The Default Applications 13 1 13 1 Application 1 Basic S...

Страница 10: ...onal Input and Output Terminals F300 F330 15 6 15 4 Analog Input and Output F400 F480 15 8 15 5 Multi stage Speed Control F500 F580 15 10 15 6 Auxiliary Functions F600 F670 15 11 15 7 Timing Control a...

Страница 11: ...roduct Code Input voltage 1 1 Phase 230V 240V 2 3 Phase 230V 240V 4 3 Phase 380V 480V Industry Rated current A XXXX OOO O Product model Frame Size mm 1 2 3 4 5 F Built in filter N without built in fil...

Страница 12: ...1 1 0 8 0 6 2 5 10G 41 0010 XX 0 37 1 5 1 2 1 5 0 10G 41 0015 XX 0 55 2 1 1 8 1 5 5 5 10G 42 0020 XX 0 75 3 2 1 2 6 5 10G 42 0030 XX 1 1 4 3 2 3 10 2 10G 42 0040 XX 1 5 5 4 2 4 11 0 10G 42 0065 XX 2...

Страница 13: ...lor and detachable one side door hinge structure adopted for front cover convenient for wiring and maintenance Taking 10G 46 0060 for instance its appearance and structure are shown below 2 1 Designed...

Страница 14: ...ges the modulation rate can be adjusted automatically so that the output voltage is unchanged Operation Function Frequency Setting Analog signal 0 5V 0 10V 0 20mA keypad terminal keys external control...

Страница 15: ...rs above each other you need additional ventilation Never touch the internal elements for 15 minutes after power goes off Wait until it is completely discharged Input terminals R S and T are connected...

Страница 16: ...30C 40C 45C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 1 5 30C 40C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 50C 2 2 35C 40C 50C 50C 50C...

Страница 17: ...arge the inverter within half a year to prevent the electrolytic capacitors being damaged The charging time should be longer than 5 hours 4 3 Daily Maintenance Environment temperature humidity dust an...

Страница 18: ...Code A B C D H Opening size 1001 00 00 124 74 120 70 26 121 71 4 LEDs indicate working status RUN while running FWD running forward and FRQ when the MMI is showing frequency LED shows running frequenc...

Страница 19: ...e Opening size E F L N M 1001 00 00 170 110 22 102 142 5 2 2 Port of control panel Pins 1 2 3 4 5 6 7 8 8 core None 5V Grounding Grounding Signal 1 Signal 2 Signal 3 Signal 4 The default length of rem...

Страница 20: ...n code keep pressing O key for 3s inverter will be stopped if stop command is controlled by keypad 6 1 Parameters Setting This inverter has numerous function parameters that the user can modify to eff...

Страница 21: ...esigned as Function Code Switchover in a Code Group or between Two Code Groups so that parameters setting becomes convenient and simple Press M key so that the keypad controller will display function...

Страница 22: ...ut phase loss for input Communication error Flycatching fault respectively AErr Err5 Analog line disconnected PID parameters are set wrong ESP External coast stop terminal is closed ESP will be displa...

Страница 23: ...rnal Dimension A B H H1 mm Max Weight kg Mounting Size W L Mounting Bolt 1 80 135 138 153 1 25 70 128 M4 2 106 150 180 195 1 76 94 170 M4 3 138 152 235 250 2 96 126 225 M5 4 156 170 265 280 4 9 146 25...

Страница 24: ...7 2 Installation Connection AC10 Inverter Metal Cover Layout Note H is the size of inverter without grounding plate H1 is the size of inverter with grounding plate www comoso com...

Страница 25: ...Braking resistor 1 phase 230V 1 1kW 2 2kW L1 R L2 SL3 T P B U V W 220V 240V 1 phase input Braking resistor 3 phase output 3 phase 230V 0 2kW 0 75kW L1 L2 L3 P B U V W 220V 240V 3 phase input Braking r...

Страница 26: ...als for single phase Output Terminal U V W Inverter power output terminal connected to motor Grounding Terminal Inverter grounding terminal Braking Terminal P B External braking resistor Note no Termi...

Страница 27: ...the voltages and currents on the inverter power supply and output sides include harmonics measurement data depends on the instruments used and circuits measured When instruments for commercial freque...

Страница 28: ...utput voltage Output side current I2 U V and W line currents Moving iron type AC Ammeter Current should be equal to or less than rated inverter current Difference between the phases is 10 or lower of...

Страница 29: ...tting of AI2 is 0 20mA AI2 GND Self contained Power supply Ground Ground terminal of external control signal voltage control signal or current source control signal is also the ground of 10V power sup...

Страница 30: ...PNP mode If NPN mode is adopted please slide the toggle switch to the end of NPN Wiring for control terminals as follows 7 5 1Wiring for positive source electrode NPN mode 7 5 2Wiring for active sour...

Страница 31: ...cording to requirement Instructions of choosing NPN mode or PNP mode 1 There is a toggle switch J7 near to control terminals Please refer to Figure 7 2 2 When turning J7 to NPN DI terminal is connecte...

Страница 32: ...as not every terminal needs to be connected in each mode when applied Note 1 Only connect power terminals L1 R and L2 S with power grid for single phase inverters 2 The contact capacity for 22kW and b...

Страница 33: ...Installation Connection 7 11 AC10 Inverter 30kW 180kW Basic Wiring Diagram for Three phase AC drives NPN type www comoso com...

Страница 34: ...erated by the drive may disturb the equipment nearby The degree of disturbance is dependent on the drive system immunity of the equipment wiring installation clearance and earthing methods 7 7 1 Noise...

Страница 35: ...be shielded and the shielding layer should be grounded The signal cables should be placed inside a metal tube and should be located as far away as possible from the input output cables of the drive I...

Страница 36: ...st Shared earthing pole good Shared earthing cable not good Note 1 In order to reduce the earthing resistance flat cable should be used because the high frequency impedance of flat cable is smaller th...

Страница 37: ...ing the product against high order harmonics surge leakage current Leakage Current Between Lines The line leakage current flowing through the distribution capacitors of the drive outside may cause the...

Страница 38: ...It can also suppress the radiation of the equipment Common mistakes in using power cable filter 1 Too long power cable The filter inside the cabinet should be located near to the input power source Th...

Страница 39: ...ol 3 Modbus control 4 Keypad Terminal Modbus The modes of control command can be selected through the function codes F200 and F201 8 1 5 Operating status of inverter When the inverter is powered on it...

Страница 40: ...hree level menu Function code group first level menu Function code second level menu Set value of each function code third level menu 8 2 3 Setting the Parameters Setting the parameters correctly is a...

Страница 41: ...00 For example If the parameters indicated on the nameplate of the motor controlled are as follows numbers of motor poles are 4 rated power is 7 5kW rated voltage is 400V rated current is 15 4A rated...

Страница 42: ...c parameters of the motor controlled Before carrying out tuning of the parameters make sure to disconnect the motor from mechanical load to make the motor under entirely no load status It is prohibite...

Страница 43: ...eed 1440rpm 8 3 1 Frequency setting start forward running and stop using the keypad panel i Connect the wires in accordance with Table 8 1 After having checked the wiring successfully switch on the po...

Страница 44: ...running current frequency of the inverter can be changed by pressing or vii Press the O key once the motor will decelerate until it stops running viii Switch off the air switch and power off the inve...

Страница 45: ...may occur viii Switch off the switches DI3 and DI4 the motor will decelerate until it stops running ix Switch off the isolator and power off the inverter 8 3 3 Operation process of jogging operation u...

Страница 46: ...etting external analog signals For the cases with higher requirements for precision a precise multiturn potentiometer is recommended and adopt shielded wire for the wire connection with near end of th...

Страница 47: ...is a toggle switch S1 at the side of control terminals refer to Fig 8 6 S1 is used to select the voltage input range of AI1 channel When turning S1 to the input range is 0 10V when turning S1 to the i...

Страница 48: ...1 Switch 3 Switch 2 Switch 4 Analog signal range OFF OFF 0 5V voltage OFF OFF 0 5V voltage OFF ON 0 10V voltage OFF ON 0 10V voltage ON ON 0 20mA current ON ON 0 20mA current OFF OFF Reserved OFF ON 1...

Страница 49: ...f F137 3 While studying motor parameters motor does not need to be disconnected with load One inverter can only drive one motor 6 PMSM sensorless vector control is suitable for the application of high...

Страница 50: ...not limited by the Min frequency set by F112 If the starting frequency set by F109 is lower than Min frequency set by F112 inverter will start according to the setting parameters set by F109 and F110...

Страница 51: ...e if valid F119 The reference of setting accel decel time Setting range 0 0 50 00Hz 1 0 F111 Mfr s value 0 When F119 0 acceleration deceleration time means the time for inverter to accelerate decelera...

Страница 52: ...g range 0 1 3000 Mfr s value subject to inverter model F126 Jogging Deceleration Time S There are two types of jogging keypad jogging and terminal jogging Keypad jogging is valid only under stopped st...

Страница 53: ...ing Display Items 0 Current output frequency function code 1 Output rotary speed 2 Output current 4 Output voltage 8 PN voltage 16 PID feedback value 32 Temperature 64 Reserved 128 Linear speed 256 PI...

Страница 54: ...s of motor poles F804 4 drive ratio F133 1 00 transmission shaft radius R 0 05m then Transmission shaft perimeter 2 R 2 3 14 0 05 0 314 meter Transmission shaft rotary speed 60 operation frequency num...

Страница 55: ...tor parameters F140 Voltage compensation point frequency Hz Setting range 0 F142 Mfr s value 1 00 F141 Voltage compensation point 1 Setting range 0 100 Subject to inverter model F142 User defined freq...

Страница 56: ...below table Carrier wave frequency Low High Motor noise Loud Low Waveform of output current Bad Good Motor temperature High Low Inverter temperature Low High Leakage current Low High Interference Low...

Страница 57: ...will decrease Please set the value according to the situation F160 Reverting to manufacturer values Setting range 0 Invalid 1 Valid Mfr s value 0 When there is problem with inverter s parameters and m...

Страница 58: ...ng 1 Reverse running locking 2 Terminal setting Mfr s value 0 The running direction is controlled by this function code together with other speed control mode which can set the running direction of in...

Страница 59: ...given means that the target frequency will restore to the value of F113 after stop no matter the state of F220 9 PID adjusting When PID adjusting is selected the running frequency of inverter is the...

Страница 60: ...econdary frequency source only suitable for F203 4 F204 1 When F207 5 X Y the frequency is set by subtracting secondary frequency source from main frequency source If the frequency is set by main freq...

Страница 61: ...e three terminals designated in programming DI1 DI5 1 Two line operation mode 1 this mode is the most popularly used two line mode The running direction of mode is controlled by FWD REV terminals For...

Страница 62: ...lse FWD terminal impulse signal forward stop REV terminal impulse signal reverse stop CM terminal common port Note when pulse of SB1 triggers inverter will run forward When the pulse triggers again in...

Страница 63: ...to start automatically after repowered on is set by F213 F213 1 Auto starting after repowered on is valid When inverter is power off and then powered on again it will run automatically after the time...

Страница 64: ...ower down or malfunction is set by this function The function of frequency memory after power down is valid for main frequency and secondary frequency that is given by digital Because the digital give...

Страница 65: ...to instructions from F307 to F309 4 Free stop Under free stop status after stop command is given ON signal is output until inverter completely stops 5 In running status 1 Indicating that inverter is...

Страница 66: ...e alarm Warning When testing temperature reaches 80 of setting value ON signal is output When overheat protection occurs or testing value is lower than 80 of setting value ON signal stops outputting 1...

Страница 67: ...current Setting range 0 1000 Mfr s value Rated current F311 Characteristic current width Setting range 0 100 Mfr s value 10 When F300 17 or F301 17 or token characteristic current is selected this gro...

Страница 68: ...o running 58 Direction Mfr s value 11 F317 DI2 terminal function setting Mfr s value 9 F318 DI3 terminal function setting Mfr s value 15 F319 DI4 terminal function setting Mfr s value 16 F320 DI5 term...

Страница 69: ...ate is set by F211 14 DOWN frequency decreasing terminal 15 FWD terminal When start stop command is given by terminal or terminals combination running direction of inverter is controlled by external t...

Страница 70: ...2 the function is used to switch manual run and auto run 56 Manual run In the application 2 if the function is valid inverter will run manually 57 Auto running In the application 2 if the function is...

Страница 71: ...F556 F564 F572 1 0 0 0 Multi stage speed 9 F512 F527 F542 F573 1 0 0 1 Multi stage speed 10 F513 F528 F543 F574 1 0 1 0 Multi stage speed 11 F514 F529 F544 F575 1 0 1 1 Multi stage speed 12 F515 F530...

Страница 72: ...I5 valid 2 stands for DI2 valid stands for DI6 valid 3 stands for DI3 valid stands for DI7 valid 4 stands for DI4 valid stands for DI8 valid 9 3 3 Analog input monitoring The value of analog is displa...

Страница 73: ...peed control effect The upper and lower limit of analog input are set by F400 and F402 For example when F400 1 F402 8 if analog input voltage is lower than 1V system judges it as 0 If input voltage is...

Страница 74: ...s value 0 01 F407 Corresponding setting for lower limit of AI2 input Setting range 0 F409 Mfr s value 1 00 F408 Upper limit of AI2 channel input V Setting range F406 10 00 Mfr s value 10 00 F409 Corr...

Страница 75: ...AO1 output range selects 0 5V and when F423 1 AO1 output range selects 0 10V or 0 20mA When F423 2 AO1 output range selects 4 20mA When AO1 output range selects current signal please turn the switch...

Страница 76: ...analog is but the response speed will decrease Please set it according to the actual situations F460 AI1channel input mode Setting range 0 straight line mode 1 folding line mode Mfr s value 0 F461 AI...

Страница 77: ...peed type Setting range 0 3 stage speed 1 15 stage speed 2 Max 8 stage speed auto circulating Mfr s value 1 In case of multi stage speed control F203 4 the user must select a mode by F500 When F500 0...

Страница 78: ...ill run at the speed of the last stage after auto circulation is finished as follows e g F501 3 then inverter will run at auto circulation of 3 stage speed F502 100 then inverter will run 100 cycles o...

Страница 79: ...ing range 0 Invalid 1 braking before starting 2 braking during stopping 3 braking during starting and stopping Mfr s value 0 F601 Initial Frequency for DC Braking Hz Setting range 0 20 5 00 Mfr s valu...

Страница 80: ...00 Mfr s value 1 phase 130 3 phase 140 F610 Stalling Protection Judging Time S Setting range 0 1 3000 0 Mfr s value 60 0 F607 is used to set selection of stalling adjusting function Voltage control wh...

Страница 81: ...aking transistor is set by F611 which is in units of V When DC bus voltage is higher than the setting value of this function dynamic braking starts braking unit starts working After DC bus voltage is...

Страница 82: ...raking module will start dynamic braking according to duty ratio which is adjusted by the bus line voltage The higher bus line voltage is the greater duty ratio is and the better braking effect is The...

Страница 83: ...ee stop signal the inverter will execute free stop command after waiting some time instead of stopping immediately Delay time is set by F701 F702 Fan control mode 0 controlled by temperature 1 Running...

Страница 84: ...rload coefficient When the output frequency is lower than 10Hz the heat dissipation effect of common motor will be worse So when running frequency is lower than 10Hz the threshold of motor overload va...

Страница 85: ...dog fault Err6 67 Overcurrent OC2 F709 Record of Malfunction Type for Last but One F710 Record of Malfunction Type for Last but Two F711 Fault Frequency of The Latest Malfunction F712 Fault Current of...

Страница 86: ...nce to avoid mis protection The greater the set value is the longer the filtering time constant is and the better for the filtering effect F737 Over current 1 protection Setting range 0 Invalid 1 Vali...

Страница 87: ...stationary tuning Mfr s value 0 F801 Rated power kW Setting range 0 75 1000 F802 Rated voltage V Setting range 1 440 F803 Rated current A Setting range 0 1 6500 F804 Number of motor poles Setting rang...

Страница 88: ...eplate of the motor If the operator is quite familiar with the motor the operator may input all the parameters F806 F809 of the motor manually 2 Parameter F804 can only be checked not modified 3 Incor...

Страница 89: ...loop KP1 Setting range 0 01 20 00 for 22kw and below 22kw 1 100 for above 22kw Subject to inverter model F814 Rotary speed loop KI1 Setting range 0 01 2 00 for 22kw and below 22kw 0 01 10 00 for abov...

Страница 90: ...hem carefully F870 PMSM back electromotive force mV rpm 0 1 999 9 valid value between lines F871 PMSM D axis inductance mH 0 01 655 35 F872 PMSM Q axis inductance mH 0 01 655 35 F873 PMSM stator resis...

Страница 91: ...iven by external analog AI2 FA02 PID feedback signal given source Setting range 1 AI1 2 AI2 Mfr s value 1 When FA02 1 PID reference feedback signal is given by external analog AI1 When FA02 2 PID refe...

Страница 92: ...increasing differential time can increase the dynamic response of PID closed loop system But if P is too high I is too low or D is too high system will not be steady PID adjusting period is set by FA...

Страница 93: ...ergency fire mode 2 when the terminal is valid inverter will run at the frequency of FA60 FA60 Running frequency of emergency fire Setting range F112 F111 Mfr s value 50 0 When the emergency fire mode...

Страница 94: ...Analog input AI1 2 Analog input AI2 0 FC07 Torque reference coefficient analogue input 0 3 000 3 000 FC09 Torque reference command value 0 300 0 100 0 FC07 when input given torque reaches max value FC...

Страница 95: ...Digital given FC30 1 Analog input AI1 2 Analog input AI2 0 FC29 Driving torque limit coefficient 0 3 000 3 000 FC30 Driving torque limit 0 300 0 200 0 FC31 Re generating torque limit channel 0 Digital...

Страница 96: ...ase loss with input power check if power input is normal check if parameter setting is correct PF0 Output Phase Loss Motor is broken Motor wire is loose Inverter is broken check if wire of motor is lo...

Страница 97: ...ing Wiring correct Setting correct Too big with load Motor is damaged Malfunction protection occurs Get connected with power Check wiring Checking malfunction Reduce load Check against Table 10 1 Wron...

Страница 98: ...XX 0 37 1 5 1 2 1 5 94 10G 41 0015 XX 0 55 2 1 1 8 1 5 5 5 94 10G 42 0020 XX 0 75 3 2 1 2 6 5 94 10G 42 0030 XX 1 1 4 3 2 3 10 2 0 15 95 94 10G 42 0040 XX 1 5 5 4 2 4 11 94 10G 42 0065 XX 2 2 7 5 7 0...

Страница 99: ...3A Inverter Address Function Code Data Length Data 1 Data N High order byte of LRC Low or der byte of LRC Return 0X0D Line Feed 0X0A RTU mode Start Address Function Data CRC check End T1 T2 T3 T4 Inve...

Страница 100: ...complement 12 5 2 RTU Mode Cyclical Redundancy Check CRC The CRC field is two bytes containing a 16 bit binary value The CRC is started by first preloading a 16 bit register to all 1 s Then a process...

Страница 101: ...parameters address i Use the function code as parameter address General Series High order byte 01 0A hexadecimal Low order byte 00 50 max range hexadecimal Function code range of each partition is no...

Страница 102: ...by mode 0X01 Forward running 0X02 Reverse running 0X04 Over current OC 0X05 DC over current OE 0X06 Input Phase loss PF1 0X07 Frequency Over load OL1 0X08 Under voltage LU 0X09 Overheat OH 0X0A Motor...

Страница 103: ...speed 7 0111 Stage speed 8 1000 Stage speed 9 1001 Stage speed 10 1010 Stage speed 11 1011 Stage speed 12 1100 Stage speed 13 1101 Stage speed 14 1110 Stage speed 15 1111 None 1014 Reserved 1015 AO1...

Страница 104: ...to 1 Command meaning 0001 Illegal function code 0002 Illegal address 0003 Illegal data 0004 Slave fault note 2 Note 2 Illegal response 0004 appears below two cases Do not reset inverter when inverter...

Страница 105: ...4 F203 Main frequency source X 0 Digital setting memory 1 External analog AI1 2 External analog AI2 3 Reserved 4 Stage speed control 5 No memory by digital setting 6 Reserved 7 Reserved 8 Reserved 9 P...

Страница 106: ...to communication failure but higher current to certain elements as well 12 9 Grounding and Terminal Terminal resistance of 120 will be adopted for terminal of RS485 network to diminish the reflection...

Страница 107: ...max value of function code is 1 Slave fault Eg 2 Read output frequency output voltage output current and current rotate speed from N0 2 inverter Host Query Address Function First Register Address Hi...

Страница 108: ...1 Illegal function code assumption Eg4 Read the value of F113 F114 from NO 2 inverter Host Query Address Function Register Address Hi Register Address Lo Register Count Hi Register Count L0 CRC Lo CRC...

Страница 109: ...ontrol using a manual or auto set point Application 3 supplies speed control using preset speeds Application 4 supplies speed control using terminal Application 5 supplies speed control using PID Cont...

Страница 110: ...V F F803 Rated current 0 Linear compensation 1 Square compensation F137 V F compensation 50 60 Hz 0 Running frequency Running current Analog input AI1 Running voltage Output torque PC PLC control Targ...

Страница 111: ...setting 58 direction F318 DI3 terminal function setting 52 jogging terminal no direction F319 DI4 terminal function setting 2 stop terminal F320 DI5 terminal function setting 8 free stop terminal F43...

Страница 112: ...BK Coast stop 1 2 3 5 6 4 7 8 9 10 11 12 13 14 15 16 17 18 TA TB TC 1 DO 24V CM DI1 DI2 DI3 DI4 DI5 10V 1 AI 2 AI GND 1 AO REF Direction Auto manual select Manual run Auto run Manual auto select F803...

Страница 113: ...al function setting 55 auto manual switchover F319 DI4 terminal function setting 58 direction F320 DI5 terminal function setting 8 free stop F431 AO1 analog output signal selecting 0 running frequency...

Страница 114: ...ompensation F108 Password F803 Motor rated current F112 Min frequency F115 Decel ti me Application 3 Current li mit F803 Rated current I FEBK V F SHAPING F115 Decel ti me Speed demand F114 Acc l e ti...

Страница 115: ...quency source selecting 1 X Y F316 DI1 terminal function setting 56 manual running F317 DI2 terminal function setting 3 mutiple stage speed 1 F318 DI3 terminal function setting 4 mutiple stage speed 2...

Страница 116: ...uency F114 Acc l e ti me F810 Motor rated frequency F124 Jog setpoint F209 Stop mode F137 Torque compensation F138 Linear compensation F108 Password F803 Motor rated current F112 Min frequency F115 De...

Страница 117: ...l setting memory F208 Terminal two line three line operation selecting 1 Two line operation mode 1 F316 DI1 terminal function setting 15 FWD terminal F317 DI2 terminal function setting 13 UP frequency...

Страница 118: ...alog output signal select PID control FA19 I FA20 P TA TC Given source Current limit PWM control CT VT V F F V V F F138 Linear compensation F803 Rated current 0 linear compensation F137 V F compensati...

Страница 119: ...g 58 forward running F318 DI3 terminal function setting 52 direction F319 DI4 terminal function setting 2 stop F320 DI5 terminal function setting 8 free stop F431 AO1 analog output signal selecting 0...

Страница 120: ...ial environments EN 61000 6 4 2007 Electromagnetic compatibility EMC Part 6 4 General standards Emission standard for residential commercial and light industrial environments UL508C Standard for Safet...

Страница 121: ...in parallel 14 2 2 EMC Directive When installed in accordance with this manual the product will comply with the electromagnet compatibility directive 2004 108 EC The following information is provided...

Страница 122: ...dings used for domestic purposes Note Houses apartments commercial premises or offices in a residential building are examples of first environment locations Second Environment Environment that include...

Страница 123: ...ce 10 m For category C1 if the field strength measurement at 10 m cannot be made because of high ambient noise levels or for other reasons measurement may be made at 3 m If the 3 m distance is used th...

Страница 124: ...n Length Limit Unlimited Motor Cable Cable Type Screened Armoured Segregation From all other wiring noisy Screen to Earth Both ends Max Cable Length 30 meters External Filter to Drive Cable Type Scree...

Страница 125: ...31 0045 XX JJS 15 15A 10G 32 0050 XX 10G 32 0070 XX 10G 32 0100 XX JJS 25 25A 10G 11 0015 XX 10G 11 0025 XX 10G 11 0035 XX 10G 11 0045 XX JJS 15 15A 10G 12 0050 XX 10G 12 0070 XX 10G 12 0010 XX JJS 2...

Страница 126: ...Wiring termals shall be marked to indicate the proper connections for power supply and load or a wiring diagram coded to the terminal marking shall be securely attached to the device l Use 60 75 o C...

Страница 127: ...3 STR SOL 10G 47 0750 XX Input and Output Terminal Block 96 0 3 STR SOL 10G 47 0900 XX Input and Output Terminal Block 96 0 1 10G 48 1100 XX Input and Output Terminal Block 96 0 1 0 10G 48 1500 XX Inp...

Страница 128: ...G 31 0025 XX 10G 31 0035 XX 10G 31 0045 XX 10G 32 0050 XX 10G 32 0070 XX 10G 32 0100 XX 10G 11 0015 XX 10G 11 0025 XX 10G 11 0035 XX 10G 11 0045 XX 10G 12 0050 XX 10G 12 0070 XX 10G 12 0010 XX 10G 41...

Страница 129: ...10 Holding Time of Starting Frequency S 0 0 999 9 0 0 F111 Max Frequency Hz F113 590 0Hz 50 00 F112 Min Frequency Hz 0 00Hz F113 0 50 F113 Target Frequency Hz F112 F111 50 00 F114 1 st Acceleration Ti...

Страница 130: ...ed 2048 Output power 4096 Output torque 0 1 2 4 8 15 F132 Display Items of Stop 0 frequency function code 1 Keypad jogging 2 Target rotary speed 4 PN voltage 8 PID feedback value 16 Temperature 32 Res...

Страница 131: ...100 63 F150 User defined frequency point 6 F148 F118 40 00 F151 User defined voltage point 6 0 100 81 F152 Output voltage corresponding to turnover frequency 10 100 100 F153 Carrier frequency setting...

Страница 132: ...source X 0 Digital setting memory 1 External analog AI1 2 External analog AI2 3 Reserved 4 Stage speed control 5 No memory by digital setting 6 Reserved 7 Reserved 8 Reserved 9 PID adjusting 10 MODBUS...

Страница 133: ...ction memory 0 Invalid 1 Valid 0 F213 Auto starting after repowered on 0 invalid 1 valid 0 F214 Auto starting after reset 0 invalid 1 valid 0 F215 Auto starting delay time 0 1 3000 0 60 0 F216 Times o...

Страница 134: ...ncy arrival output 16 overheat pre alarm 17 over latent current output 18 Analog line disconnection protection 19 Reserved 20 Zero current detecting output 21 DO1 controlled by PC PLC 22 Reserved 23 T...

Страница 135: ...over terminal 32 Fire pressure switchover 33 Emergency fire control 34 Accel decel switchover 2 37 Common open PTC heat protection 38 Common close PTC heat protection 48 High frequency switchover 52 J...

Страница 136: ...e Change F400 Lower limit of AI1 channel input 0 00 F402 0 01 F401 Corresponding setting for lower limit of AI1 input 0 F403 1 00 F402 Upper limit of AI1 channel input F400 10 00 10 00 F403 Correspond...

Страница 137: ...AI2 6 Output torque 7 Given by PC PLC 8 Target frequency 0 F432 AO2 analog output signal selecting 1 F433 Corresponding current for full range of external voltmeter 0 01 5 00 times of rated current 2...

Страница 138: ...requency setting for stage 3 speed F112 F111 15 00Hz F507 Frequency setting for stage 4 speed F112 F111 20 00Hz F508 Frequency setting for stage 5 speed F112 F111 25 00Hz F509 Frequency setting for st...

Страница 139: ...Braking efficiency During Stop 0 100 10 F604 Braking Lasting Time Before Starting 0 00 30 00 0 50 F605 Braking Lasting Time During Stopping 0 00 30 00 0 50 F606 Reserved F607 Selection of Stalling Adj...

Страница 140: ...on Setting Range Mfr s Value Change F700 Selection of terminal free stop mode 0 free stop immediately 1 delayed free stop 0 F701 Delay time for free stop and programmable terminal action 0 0 60 0s 0 0...

Страница 141: ...tion but One F717 Fault Frequency of Last Malfunction but Two F718 Fault Current of Last Malfunction but Two F719 Fault PN Voltage of Last Malfunction but Two F720 Record of Overcurrent Protection Fau...

Страница 142: ...id 1 Rotating tuning 2 Stationary tuning 0 F801 Rated Power 0 2 1000kW F802 Rated Voltage 1 440V F803 Rated Current 0 1 6500A F804 Number of Motor Poles 2 100 4 F805 Rated Rotary Speed 1 30000 F806 St...

Страница 143: ...MSM back electromotive force mV rpm 0 1 999 9 Subject to inverter model F871 PMSM D axis inductance mH 0 01 655 35 Subject to inverter model F872 PMSM Q axis inductance mH 0 01 655 35 Subject to inver...

Страница 144: ...eedback 1 Negative feedback 1 FA07 Sleep function selection 0 Valid 1 Invalid 0 FA09 Min frequency of PID adjusting Hz Max F112 0 1 F111 5 00 FA10 Sleep delay time S 0 500 0 15 0 FA11 Wake delay time...

Страница 145: ...rque reference coefficient 0 3 000 3 000 FC08 Reserved FC09 Torque reference command value 0 300 0 100 0 FC10 FC13 Reserved FC14 Offset torque reference source 0 Digital given FC17 1 Analog input AI1...

Страница 146: ...2 Analog input AI2 0 FC34 Re generating torque limit coefficient 0 3 000 3 000 FC35 Re generating torque limit 0 300 0 200 00 FC36 FC40 Reserved Note indicating that function code can only be modified...

Страница 147: ...r com IE Ireland Dublin Tel 353 0 1 466 6370 parker ireland parker com IN India Mumbai Tel 91 22 6513 7081 85 IT Italy Corsico MI Tel 39 02 45 19 21 parker italy parker com JP Japan Tokyo Tel 81 0 3 6...

Отзывы: