Modbus Communication
12-5
AC10 Inverter
Reading
parameter
address
Function
Remarks
100A
Read integer power value
The integer power value is read by PC.
100B
DI terminal status
DI1~DI8—bit0~bit7
100C
Terminal output status
bit0-OUT1 bit2-fault relay
100D
AI1
0~4095 read input analog digital value
100E
AI2
0~4095 read input analog digital value
1010
Reserved
1011
Reserved
1012
Reserved
1013
Present-stage speed value
Monitoring in which stage speed inverter is.
0000 Stage speed1
0001 stage speed 2
0010 Stage speed 3
0011 Stage speed 4
0100 Stage speed 5
0101 Stage speed 6
0110 Stage speed 7
0111 Stage speed 8
1000 Stage speed 9
1001 Stage speed 10
1010 Stage speed 11
1011 Stage speed 12
1100 Stage speed 13
1101 Stage speed 14
1110 Stage speed 15
1111 None
1014
Reserved
1015
AO1
(
0~100.00
)
Monitoring analog output percent
1016
AO2
(
0~100.00
)
Monitoring analog output percent
1017
Current speed
Monitoring current speed.
1018
Read accurate power value Correct the power to 1 decimal place.
12.6.3 Control commands
Parameters
Address
Parameters Description
(
write only
)
2000
Command meaning:
0001
:
Forward running (no parameters
)
0002
:
Reverse running
(
no parameters
)
0003
:
Deceleration stop 0004
:
Free stop
0005
:
Forward jogging start
0006
:
Forward jogging stop
0007
:
Reserved 0008
:
Run
(
no directions
)
0009
:
Fault reset
000A: Forward jogging stop 000B: Reverse jogging stop
www.comoso.com