8-4
Operation and Simple Running
AC10 Inverter
8.2.8
Operation process of simple running
Table 8-1 Brief Introduction to Inverter Operation Process
Process
Operation
Reference
Installation and operation
environment
Install the inverter at a location meeting the technical specifications and
requirements of the product. Mainly take into consideration the
environment conditions (temperature, humidity, etc) and heat radiation of
the inverter, to check whether they can satisfy the requirements.
See
Chapters I,
2, 3.
Wiring of the inverter
Wiring of input and output terminals of the main circuit; wiring of
grounding; wiring of switching value control terminal, analog terminal
and communication interface, etc.
See
Chapters 7
& 8.
Checking before
getting energised
Make sure that the voltage of input power supply is correct; the input
power supply loop is connected with a breaker; the inverter has been
grounded correctly and reliably; the power cable is connected to the
power supply input terminals of inverter correctly (R/L1, S/L2 terminals
for single-phase power grid, and R/L1, S/L2, and T/L3 for three-phase
power grid); the output terminals U, V, and W of the inverter are
connected to the motor correctly; the wiring of control terminals is
correct; all the external switches are preset correctly; and the motor is
under no load (the mechanical load is disconnected from the motor).
See
Chapter 7
Checking immediately after
energised
Check if there is any abnormal sound, smell with the inverter. Make
sure that the display of keypad panel is normal, without any fault alarm
message. In case of any abnormality, switch off the power supply
immediately.
See Chapter
8
Inputting the parameters
indicated on the motor’s
nameplate correctly, and
measuring the motor’s
parameters.
Make sure to input the parameters indicated on the motor nameplate
correctly, and study the parameters of the motor. The users shall check
carefully, otherwise, serious problems may arise during running.
Before initial running with vector control mode, carry out tuning of
motor parameters, to obtain accurate electric parameters of the motor
controlled. Before carrying out tuning of the parameters, make sure to
disconnect the motor from mechanical load, to make the motor under
entirely no load status. It is prohibited to measure the parameters when
the motor is at a running status.
See
description
of
parameter
group
F800~F830
Setting running control
parameters
Set the parameters of the inverter and the motor correctly, which mainly
include target frequency, upper and lower frequency limits,
acceleration/deceleration time, and direction control command, etc. The
user can select corresponding running control mode according to actual
applications.
See
description
of
parameter
group.
Checking under
no load
With the motor under no load, start the inverter with the keypad or
control terminal. Check and confirm running status of the drive system.
Motor’s status: stable running, normal running, correct rotary direction,
normal acceleration/deceleration process, free from abnormal vibration
and abnormal noise.
Inverter’ status: normal display of the data on keypad panel, normal
running of the fan, normal acting sequence of the relay, free from the
abnormalities like vibration or noise.
In case of any abnormality, stop and check the inverter immediately.
See
Chapter 8.
Checking under with
Load
After successful test run under no load, connect the load of drive
system properly. Start the inverter with the keypad or control terminal,
and increase the load gradually. When the load is increased to 50%
and 100%, keep the inverter run for a period respectively, to check if
the system is running normally. Carry out overall inspection over the
inverter during running, to check if there is any abnormality. In case of
any abnormality, stop and check the inverter immediately.
Checking during running
Check if the motor is running stable, if the rotary direction of the motor
is correct, if there is any abnormal vibration or noise when the motor is
running, if the acceleration/deceleration process of the motor is stable,
if the output status of the inverter and the display of keypad panel is
correct, if the blower fan is run normally, and if there is any abnormal
vibration or noise. In case of any abnormality, stop the inverter
immediately, and check it after switching off the power supply.