Hyperchill (ICE001)
14
English
6
Troubleshooting
THE OUTLET WATER
TEMPERATURE
EXCEEDS THE SET
VALUE
FAULT
CAUSE
YES
NO
COMPRESSOR STOPS DUE
TO OPERATION OF THE
HIGH PRESSURE SWITCH
PRESSURE
SWITCH
BROKEN OR
WRONGLY
CALIBRATED
EXCESSIVE
WATER
FLOW, HIGH
THERMAL LOAD
REDUCE THE
FLOW RATE OF
THE WATER TO
BE COOLED
COMPRESSOR
COMPONENTS
DETERIORATED
REFRIGERANT
FILTER
CLOGGED
INSUFFICIENT
WATER FLOW
COMPRESSOR
RUNS FOR
LONG PERIODS,
NOISY
COMPRESSOR SUCTION,
LIQUID LINE
FROSTED UP
REPLACE
PRESSURE SWITCH
REPLACE
THE FILTER
INCREASE THE
FLOW RATE OF
THE FLUID TO
BE COOLED
REPAIR OR
REPLACE
COMPRESSOR
HIGH
AMBIENT
TEMPERATURE
CONDENSER
FINS
DIRTY
CONDENSER
SURFACES
CLOGGED
LEAKS IN
CIRCUIT,
SYSTEM
DISCHARGED
REFRIGERANT
FILTER
CLOGGED
RETURN THE
AMBIENT
TEMPERATURE TO
BELOW THE
SPECIFIED LIMIT
CLEAN THE FINS
OF THE
CONDENSER
CLEAR THE FRONT
SURFACE
OF THE
CONDENSER
CHECK
FOR LEAKS,
ELIMINATE THEM,
CHARGE
THE CIRCUIT
REPLACE
THE FILTER
REMEDY
NO
YES
YES
YES
YES
NO
NO
NO
YES
YES
YES
YES
YES
NO
NO
Содержание Hyperchill ICE001
Страница 1: ...Manuale d uso User manual Manual de uso DATE 03 11 2009 Rev 3 CODE 271783 Hyperchill ICE001 ...
Страница 2: ......
Страница 7: ...5 Hyperchill ICE001 Italiano 4 5 Gestione parametri SET S1 ...
Страница 14: ...Hyperchill ICE001 12 English 4 5 Parameter management SET S1 ...
Страница 21: ...19 Hyperchill ICE001 Español 4 5 Gestión de los parámetros SET S1 ...
Страница 26: ...Hyperchill ICE001 24 7 3 Dimensions ...
Страница 28: ...Hyperchill ICE001 26 7 5 Circuit diagram A1 ...
Страница 29: ...27 Hyperchill ICE001 7 6 Wiring diagram Sheet 1 of 2 ...
Страница 30: ...Hyperchill ICE001 28 Wiring diagram Sheet 2 of 2 ...
Страница 31: ......