13
Hyperchill (ICE001)
English
4.6
Alarms management
4.6.1 Alarms
CODE
Led
Description
Reset
E0
L3
Control sensor error
M
EE
L3
Data acquisition error
M
4.7
Automatic restart
In the event of a power failure, when power is restored the chiller
will assume the On---Off status held at the moment the power was
lost.
5
Maintenance
a) The machine is designed and built to guarantee continuous
operation; however, the life of its components depends on the
maintenance performed.
b) When requesting assistance or spare parts, identify the ma-
chine (model and serial number) by reading the dataplate lo-
cated on the unit.
c) Circuits containing 6 kg or more of refrigerant fluid are
checked to identify leaks at least once a year.
Circuits containing 30 kg or more of refrigerant fluid are
checked to identify leaks at least once every six months.
(CE842/2006 art. 3.2.a, 3.2.b).
d) For machines containing 3 kg or more of refrigerant fluid, the
operator must keep a record stating the quantity and type of
refrigerant used, an quantities added and that recovered dur-
ing maintenance operations, repairs and final disposal
(CE842/2006 art. 3.6). An example of this record sheet can be
downloaded from the site: www.dh---hiross.com.
5.1
General instructions
!
Before performing any maintenance, make sure the power
to the refrigerator is disconnected.
Y
Always use the Manufacturer’s original spare parts: other-
wise the Manufacturer is relieved of all liability regarding ma-
chine malfunctioning.
Y
In case of refrigerant leakage, contact qualified and author-
ized personnel.
Y
The Schrader valve must only be used in case of machine
malfunction: otherwise any damage caused by incorrect refriger-
ant charging will not be covered by the warranty.
5.2
Preventive maintenance
To guarantee lasting maximum chiller efficiency and reliability,
carry out:
a)
Z
every 4 months
--- clean the condenser fins and make
sure compressor electrical absorption is within the dataplate
values;
b)
Z
Every 3 years ---
installation of kit for maintenance every
3 years.
The following are available (see par. 7.4):
a)
kit for maintenance every 3 years
;
b)
service kit
;
1. compressor kit;
2. fan kit;
3. expansion valve kit;
4. P3 pump kit;
c)
individual spare parts.
5.3
Refrigerant
Z
Charging: any damage caused by incorrect charging carried out
by unauthorized personnel will not be covered by the warranty.
Y
At normal temperature and pressure, the R407C refrigerant
is a colourless gas classified in SAFETY GROUP A1 --- EN378
(group 2 fluid according to Directive PED 97/23/EC);
GWP (Global Warming Potential) = 1652,5.
!
In case of refrigerant leakage, air the room.
5.4
Dismantling
Z
The refrigerant and the lubricating oil contained in the circuit
must be recovered in conformity with current local environmen-
tal regulations.
The refrigerant fluid is recovered before final scrapping of the
equipment (CE 842/2006 art.4.4).
%
RECYCLING
DISPOSAL
frame and panels
steel/epoxy resin polyester
pipes/collectors
copper/aluminium/carbon steel
pipe insulation
NBR rubber
compressor
steel/copper/aluminium/oil
condensator
steel/copper/aluminium
pump
steel/cast iron/brass
fan
aluminium
refrigerant
R407C (HFC)
valve
brass/copper
electrical cable
copper/PVC
Содержание Hyperchill ICE001
Страница 1: ...Manuale d uso User manual Manual de uso DATE 03 11 2009 Rev 3 CODE 271783 Hyperchill ICE001 ...
Страница 2: ......
Страница 7: ...5 Hyperchill ICE001 Italiano 4 5 Gestione parametri SET S1 ...
Страница 14: ...Hyperchill ICE001 12 English 4 5 Parameter management SET S1 ...
Страница 21: ...19 Hyperchill ICE001 Español 4 5 Gestión de los parámetros SET S1 ...
Страница 26: ...Hyperchill ICE001 24 7 3 Dimensions ...
Страница 28: ...Hyperchill ICE001 26 7 5 Circuit diagram A1 ...
Страница 29: ...27 Hyperchill ICE001 7 6 Wiring diagram Sheet 1 of 2 ...
Страница 30: ...Hyperchill ICE001 28 Wiring diagram Sheet 2 of 2 ...
Страница 31: ......