Digiplex DGP-NE96
- 42 -
Programming Guide
Installer Quick Function Keys
Press and hold the
[0]
key and then enter the
[
INSTALLER
CODE
]
. Then press one of the following function keys:
Automatic Report Code List
[
STAY
]
Test Report:
Sends the “Test Report” report code programmed in section
[3902]
to the monitoring station.
[
FORCE
]
Call WinLoad Software:
Will dial the PC telephone number programmed in section
[3010]
in order to initiate communication with a computer
using the WinLoad software.
[
ARM
]
Answer WinLoad Software:
Will force the control panel to answer a call made by the Monitoring Station that is using the WinLoad software.
[
DISARM
]
Cancel Communication:
Cancels all communication with the WinLoad software or with the Monitoring Station until the next reportable event.
[
MEM
]
Installer Test Mode:
The installer test mode will allow you to perform walk tests where the bell or siren will squawk to indicate opened zones.
Press the
[
MEM
]
button again to exit. Partitions cannot be armed if the Installer Test Mode is enabled.
[
TRBL
]
Start Module Scan:
The keypad will display the serial number of each module on the combus.
[
ACC
]
Combus Voltmeter:
To verify if the combus is supplying sufficient power, press and hold the
[0]
key, enter the
[
INSTALLER
CODE
]
and press the
[
ACC
]
button. A reading of 12.3V or lower indicates that the voltage is too low. The voltage may drop during the control panel battery test.
System Event
Default Contact ID Report Code
when using sections [4032] to [4037]
Default SIA Report Code
when using sections [4032] to [4037]
Arming with Master Code (##)
3 4A1 - Close by user
CL - Closing Report
Arming with User Code (##)
3 4A1 - Close by user
CL - Closing Report
Arming with Keyswitch (##)
3 4A9 - Keyswitch Close
CS - Closing Keyswitch
Auto Arming
3 4A3 - Automatic Close
CA - Automatic Closing
Arm with PC software
3 4A7 - Remote arm/disarm
CQ - Remote Arming
Late To Close
1 4A4 - Late to Close
OT - Late to Close
No Movement
1 4A4 - Late to Close
NA - No Activity
Partial arming
1 456 - Partial Arm
CG - Close Area
Quick arming
3 408 - Quick arm
CL - Closing Report
Disarm with Master Code (##)
1 4A1 - Open by user
OP - Opening Report
Disarm with User Code (##)
1 4A1 - Open by user
OP - Opening Report
Disarm with Keyswitch (##)
1 4A9 - Keyswitch Open
OS - Opening Keyswitch
Disarm after alarm with Master Code (##)
1 4A1 - Open by user
OP - Opening Report
Disarm after alarm with User Code (##)
1 4A1 - Open by user
OP - Opening Report
Disarm after alarm with Keyswitch (##)
1 4A1 - Keyswitch Open
OS - Opening Keyswitch
Cancel alarm with Master Code (##)
1 4A6 - Open by user
OR - Disarm From Alarm
Cancel alarm with User Code (##)
1 4A6 - Open by user
OR - Disarm From Alarm
Cancel alarm with Keyswitch (##)
1 4A6 - Keyswitch Open
OS - Opening Keyswitch
Auto Arming Cancellation
1 464 - Auto-Arm Time Extended
CE - Closing Extend
Disarm with PC software
1 4A7 - Remote arm/disarm
OQ - Remote Disarming
Disarm after an alarm with PC software
1 4A7 - Remote arm/disarm
OR - Disarm From Alarm
Quick Disarm
1 408 - Quick Disarm
OP - Opening Report
Zone Bypassed (##)
1 57A - Zone bypass
UB - Untyped Zone Bypass
Zone alarm (##)
1 13A - Burglary Alarm
BA - Burglary Alarm
Fire alarm (##)
1 11A - Fire alarm
FA - Fire Alarm
Zone alarm restore (##)
3 13A - Burglary Alarm Restore
BH - Burglary Alarm Restore
Fire alarm restore (##)
3 11A - Fire alarm Restore
FH - Fire Alarm Restore
24Hr Gas alarm (##)
1 13A - Burglary Alarm
GA - Gas Alarm
24Hr Heat alarm (##)
1 13A - Burglary Alarm
KA - Heat Alarm
24Hr Water alarm (##)
1 13A - Burglary Alarm
WA - Water Alarm
24Hr Freeze alarm (##)
1 13A - Burglary Alarm
ZA - Freeze Alarm
24Hr Gas alarm restore (##)
3 13A - Burglary Alarm Restore
GR - Gas Alarm Restore
24Hr Heat alarm restore (##)
3 13A - Burglary Alarm Restore
KR - Heat Alarm Restore
24Hr Water alarm restore (##)
3 13A - Burglary Alarm Restore
WR - Water Alarm Restore
24Hr Freeze alarm restore (##)
3 13A - Burglary Alarm Restore
ZR - Freeze Alarm Restore
Police Code
1 139 - Burglary Alarm
BM - Burglary Alarm
Panic 1 - Emergency
1 12A - Panic alarm
PA - Panic Alarm
Panic 2 - Medical
1 1AA - Medical alarm
MA - Medical Alarm
Panic 3 - Fire
1 115 - Pull Station
FA - Fire Alarm