16.5.7 Water Flow Switch Abnormality (H62)
Malfunction Decision Conditions:
During operation of heating, the water flow detected by the indoor water flow switch is used to determine water
flow error.
Malfunction Caused:
1 Air trapped in water system.
2 Faulty
water
pump.
3 Water leak in system.
4 Faulty
connector
connection.
5 Faulty water flow switch.
6 Faulty indoor unit PCB (main).
Abnormality Judgment:
Continue for 10 seconds (but no judgment for 9 minutes after compressor startup/restart).