16.5.18 Outdoor High Pressure Switch Activate (F12)
Malfunction Decision Conditions:
During operation of heating, when pressure 4.5MPa and above is detected by outdoor high pressure switch.
Malfunction Caused:
1 Faulty
water
pump.
2 Insufficient water flow rate in system.
3 Water leak in system.
4 3 way valve closed.
5 Clogged expansion valve or strainer.
6 Excessive
refrigerant.
7 Faulty outdoor high pressure sensor and switch.
8 Faulty outdoor unit PCB.
Abnormality Judgment:
Continue 4 times in 20 minutes.