45
12. Operation and Control
12.1 Basic Function
Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time
passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating
mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and
performing temperature shifting. The compressor at outdoor unit is operating following the frequency instructed by
the microcomputer at indoor unit that judging the condition according to internal water setting temperature and water
outlet temperature.
12.1.1 Internal Water Setting Temperature
Once the operation starts, control panel setting temperature will be taken as base value for temperature shifting
processes. These shifting processes are depending on the Air-to-Water Heat pump settings and the operation
environment. The final shifted value will be used as internal water setting temperature and it is updated continuously
whenever the electrical power is supplied to the unit.
12.1.2 Heating Operation
12.1.2.1 Thermostat
Control
Compressor is OFF when Water Outlet Temperature – Internal Water Setting Temperature > 2°C for
continuously 3 minutes.
Compressor is ON after waiting for 3 minutes, if the Water Outlet Temperature – Water Inlet Temperature
(temperature at thermostat OFF is triggered) <-3°C.
12.1.2.2 Thermostat
Control
(Outdoor Ambient Temperature)
Stops provide heating to room side during high outdoor ambient condition.
Control content:
Heating operation and water pump will turn OFF when outdoor ambient temperature > outdoor thermo off
tempe 3°C.
(Outdoor thermo off set temperature is set by control panel. Thermo off set temperature is between 5°C ~ 35°C)
Heating operation will resume when Outdoor ambient temperature < Outdoor thermo OFF set tempe 1°C.
12.1.2.3 Heat
Mode
Operation
Operation of heat pump provide heating capacity to room side by hot water through heating panel, floor heating or
fan coil unit.
1 3 ways valve control:
o
3 ways valve switch and fix to heating side.
2 Heat pump operates follow normal heating operation.
3 Back up heater operate follow normal operation.
4 Solar 3 way valve operates follow solar operation specification.
5 2 ways valve control:
o
2 ways valve opens.
Содержание WH-SHF09F3E5
Страница 19: ...19 4 2 Outdoor Unit Air inlet rear Air outlet Air inlet side ...
Страница 32: ...32 10 1 2 Solar Printed Circuit Board Optional ...
Страница 48: ...48 67 C 67 C 60 C 65 C 63 C 67 C 67 C ...
Страница 49: ...49 60 C 60 C 65 C 65 C 72 C ...
Страница 55: ...55 67 C 67 C 67 C 67 C ...
Страница 56: ...56 67 C 67 C 60 C 60 C 55 C 75 C ...
Страница 57: ...57 67 C 67 C 60 C 60 C 55 C 75 C ...
Страница 138: ...138 19 2 WH UH09FE5 WH UH12FE5 50 53 55 56 54a 61 60 25 59 57 58 55 56 54 66 54a 50a 50a 58 64 28 65 62 62 22 46 ...
Страница 139: ...139 2 4 1 8 7 6 9 3 21 70 70 73 23 13 68 10 4 20 5 4a 4a 19 18 12 11 13 24 27a 74 74 26 16 27 15 ...