59
12.1.6 Water Temperature Thermo Shift Setting
Switchs are ignored during “PUMPDW” = ON.
Switchs are ignored during “STATUS” = ON.
“
▲
”, “
▼
”, ”SELECT” switch are ignored if “SETTING” = OFF.
“CANCEL” switch is ignored if “SETTING” = OFF & “STATUS” = OFF.
If “SET” Switch pressed for less than 5secs, immediately enter water temperature shift setting mode.
Once enter this setting mode, “SETTING” display is ON.
This setting mode is used to easily shift the target water outlet temperature.
Outdoor
Temp.
Water
Temp.
H2O HI
+ 5
± 0
Shift value
- 5
H2O LO
OUT LO
OUT HI
OUT LO
= Low outdoor ambient set temperature
OUT HI
= High outdoor ambient set temperature
H2O LO
= Water outlet set temperature at low
outdoor ambient set temperature
H2O HI
= Water outlet set temperature at high
outdoor ambient set temperature
Shift value = Setting water temperature thermo shift
12.1.7 Outdoor Fan Motor Operation
Outdoor fan motor is adjusted according to operation condition. It starts when compressor starts operation and it
stops 30 seconds after compressor stops operation.
30 sec
Compressor:
ON
ON
Fan Speed
ON
ON
OFF
OFF
Outdoor Fan:
Содержание WH-SHF09F3E5
Страница 19: ...19 4 2 Outdoor Unit Air inlet rear Air outlet Air inlet side ...
Страница 32: ...32 10 1 2 Solar Printed Circuit Board Optional ...
Страница 48: ...48 67 C 67 C 60 C 65 C 63 C 67 C 67 C ...
Страница 49: ...49 60 C 60 C 65 C 65 C 72 C ...
Страница 55: ...55 67 C 67 C 67 C 67 C ...
Страница 56: ...56 67 C 67 C 60 C 60 C 55 C 75 C ...
Страница 57: ...57 67 C 67 C 60 C 60 C 55 C 75 C ...
Страница 138: ...138 19 2 WH UH09FE5 WH UH12FE5 50 53 55 56 54a 61 60 25 59 57 58 55 56 54 66 54a 50a 50a 58 64 28 65 62 62 22 46 ...
Страница 139: ...139 2 4 1 8 7 6 9 3 21 70 70 73 23 13 68 10 4 20 5 4a 4a 19 18 12 11 13 24 27a 74 74 26 16 27 15 ...