14 Servicing Mode
14.1. Test Run
1. Fill up the boiler tank with water. For details refer to boiler tanks installation instruction and operation instruction.
2. Antifreeze agent must be added into water circuit to prevent freezing of water when outdoor ambient temperatures is low.
Recommended antifreeze: Propylene glycol: 40% (equivalent to -20°C)
3. Set ON to the Monobloc unit and RCCB. Then, for remote control operation please refers to Monobloc unit operation
instruction.
4. For normal operation, pressure gauge reading should be in between 0.05 MPa and 0.2 MPa.
If necessary, adjust the water pump speed accordingly to obtain normal water pressure operating range. If adjust water pump
speed cannot solve the problem, contact your local authorized dealer.
14.2. Proper Pump Down Procedure
1. Make sure the OFF/ON remote control LED is OFF (no operation).
2. Press the “PUMPDW” switch on remote control to begin PUMP DOWN mode. Operate the system in PUMP DOWN mode for
10 ~ 15 minutes.
3. After 10-15 minutes, (after 1 or 2 minutes in case very low ambient temperatures (< 10
°
C)), fully close 3 way valve (Liquid
side).
4. After 3 minutes, fully close 3 way valve (Gas side).
5. Press the “OFF/ON” switch on remote control to stop PUMP DOWN mode.
6. Remove the refrigerant piping.
14.3. How To Adjust Water Flow Rate
• Before adjust the water flow rate, make sure that the total water volume in the installation is 50 litres minimum.
• The water flow rate can be adjusted with select the water pump speed on the water pump. The default setting is moderate speed
(II). Adjust it to high speed (III) and slow speed (I) if necessary (e.g. reduce the noise of running water).
Below graph shown the external static pressure (kPa) versus water flow rate (l/min).
• Flow rate characteristic of Monobloc unit is as per above mentioned.
14.4. Expansion Vessel Pre Pressure Checking
• Expansion Vessel with 10L air capacity and initial pressure of 1 bar is installed in this Monobloc unit.
• Total amount of water in system should be below 200L.
(Note: This amount of water is not include the tank unit volume)
• If total amount of water is over 200L, please add expansion vessel.
• Please keep the installation height difference of system water circuit within 7m.
(Inner volume of same Monobloc unit is about 5L)
Содержание WH-MDC09C3E5
Страница 14: ...14 4 Location of Controls and Components 4 1 Monobloc Unit ...
Страница 17: ...17 ...
Страница 18: ...18 ...
Страница 19: ...19 4 1 2 2 Weekly Timer Setting ...
Страница 20: ...20 4 1 2 3 Setting Up The Special Functions ...
Страница 21: ...21 5 Dimensions 5 1 Monobloc Unit ...
Страница 22: ...22 6 Refrigeration And Water Cycle Diagram ...
Страница 23: ...23 ...
Страница 24: ...24 7 Block Diagram 7 1 WH MDC09C3E5 ...
Страница 25: ...25 7 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Страница 26: ...26 8 Wiring Connection Diagram 8 1 WH MDC09C3E5 ...
Страница 27: ...27 ...
Страница 28: ...28 8 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Страница 29: ...29 ...
Страница 30: ...30 9 Electronic Circuit Diagram 9 1 WH MDC09C3E5 ...
Страница 31: ...31 ...
Страница 32: ...32 9 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Страница 33: ...33 ...
Страница 34: ...34 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Страница 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Страница 36: ...36 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 37: ...37 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 38: ...38 11 Installation Instruction Monobloc Unit Dimension Diagram ...
Страница 39: ...39 Main Components ...
Страница 52: ...52 Solar Priority is Set Solar Priority is Not Set ...
Страница 55: ...55 Heat Tank Heating No Priority Solar Priority Set ...
Страница 56: ...56 Heat Tank Heating No Priority Solar Priority Not Set ...
Страница 66: ...66 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Страница 67: ...67 Tank Mode Solar Priority Set Solar Priority Not Set ...
Страница 115: ...115 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Страница 118: ...118 17 10 To Remove Bottle Complete When reinstall the water pipe use grease or water at the joining ...
Страница 130: ...130 ...
Страница 134: ...134 19 2 WH MDC09C3E5 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 Water System ...