95
16.5.15. Outdoor High Pressure Switch Activate (F12)
Malfunction Decision Conditions:
During operation of cooling and heating, when pressure 4.5MPa and above is detected by outdoor high pressure switch.
Malfunction Caused:
1. Dust accumulation on the outdoor unit heat exchanger.
2. Air short circuit at outdoor unit.
3. Faulty water pump.
4. Insufficient water flow rate in system.
5. Water leak in system.
6. 2/3 way valve closed.
7. Clogged expansion valve or strainer.
8. Excessive refrigerant.
9. Faulty outdoor high pressure sensor and switch.
10. Faulty outdoor unit PCB.
Abnormality Judgment:
Continue 4 times in 20 minutes.
Содержание WH-MDC09C3E5
Страница 14: ...14 4 Location of Controls and Components 4 1 Monobloc Unit ...
Страница 17: ...17 ...
Страница 18: ...18 ...
Страница 19: ...19 4 1 2 2 Weekly Timer Setting ...
Страница 20: ...20 4 1 2 3 Setting Up The Special Functions ...
Страница 21: ...21 5 Dimensions 5 1 Monobloc Unit ...
Страница 22: ...22 6 Refrigeration And Water Cycle Diagram ...
Страница 23: ...23 ...
Страница 24: ...24 7 Block Diagram 7 1 WH MDC09C3E5 ...
Страница 25: ...25 7 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Страница 26: ...26 8 Wiring Connection Diagram 8 1 WH MDC09C3E5 ...
Страница 27: ...27 ...
Страница 28: ...28 8 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Страница 29: ...29 ...
Страница 30: ...30 9 Electronic Circuit Diagram 9 1 WH MDC09C3E5 ...
Страница 31: ...31 ...
Страница 32: ...32 9 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Страница 33: ...33 ...
Страница 34: ...34 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Страница 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Страница 36: ...36 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 37: ...37 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 38: ...38 11 Installation Instruction Monobloc Unit Dimension Diagram ...
Страница 39: ...39 Main Components ...
Страница 52: ...52 Solar Priority is Set Solar Priority is Not Set ...
Страница 55: ...55 Heat Tank Heating No Priority Solar Priority Set ...
Страница 56: ...56 Heat Tank Heating No Priority Solar Priority Not Set ...
Страница 66: ...66 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Страница 67: ...67 Tank Mode Solar Priority Set Solar Priority Not Set ...
Страница 115: ...115 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Страница 118: ...118 17 10 To Remove Bottle Complete When reinstall the water pipe use grease or water at the joining ...
Страница 130: ...130 ...
Страница 134: ...134 19 2 WH MDC09C3E5 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 Water System ...