13 Protection Control
13.1. Protection Control For All Operations
13.1.1.
Time Delay Safety Control
1. The compressor will not start for three minutes after stop of operation.
13.1.2.
30 Seconds Forced Operation
1. Once the compressor starts operation, it will not stop its operation for 30 seconds.
2. However, it can be stopped using remote control.
13.1.3.
Total Running Current Control
1. When the Monobloc unit running current exceeds X value, the compressor frequency will decrease.
2. If the Monobloc unit running current does not exceed X value, the compressor frequency will return to normal operating fre-
quency.
3. If the Monobloc unit running current continue to increase till exceed Y value, compressor will stop, and if this occurs 3 times
within 20 minutes, system will stop operation and OFF/ON remote control LED will blink (F16 error occurs).
13.1.4.
IPM (Power transistor) Prevention Control
A. Overheating Prevention Control
1. When the IPM temperature rises to 95
°
C, compressor will stop immediately.
2. Compressor will restart delay 3 minutes when the IPM temperature decreases to 90
°
C.
If this condition repeats continuously 3 times within 30 minutes, system will stop operation and OFF/ON remote control LED
will blink (F22 error occurs).
B. DC Peak Current Control
1. When the current to IPM exceeds set value of 40.1 ± 5.0 A (MDC09), 44.7 ± 5.0 A (MDC12, MDC14 and MDC16), compres-
sor will stop. Compressor will restart after three minutes.
2. If the set value exceeds again for more than 30 seconds after the compressor restarts, operation will restart after two minutes.
3. If the set value exceeds again for within 30 seconds after the compressor restarts, operation will restart after one minute. If
this condition repeats continuously for seven times, system will stop operation and OFF/ON remote control LED will blink (F23
error occurs).
13.1.5.
Compressor Overheating Prevention Control
• The compressor operating frequency is regulated in accordance to compressor tank temperature as shown in below figures.
When the compressor tank temperature exceeds 112
°
C, compressor will stop, and if this occurs 4 times within 30 minutes,
system will stop operation and OFF/ON remote control LED will blink (F20 error occurs).
09C
12C
14C
16C
Operation Mode
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
X (A)
Y (A)
Heating
22.7
27.9
24.0
27.9
25.0
27.9
26.0
27.9
Cooling
14.6
27.9
16.0
27.9
19.7
27.9
22.6
27.9
Содержание WH-MDC09C3E5
Страница 14: ...14 4 Location of Controls and Components 4 1 Monobloc Unit ...
Страница 17: ...17 ...
Страница 18: ...18 ...
Страница 19: ...19 4 1 2 2 Weekly Timer Setting ...
Страница 20: ...20 4 1 2 3 Setting Up The Special Functions ...
Страница 21: ...21 5 Dimensions 5 1 Monobloc Unit ...
Страница 22: ...22 6 Refrigeration And Water Cycle Diagram ...
Страница 23: ...23 ...
Страница 24: ...24 7 Block Diagram 7 1 WH MDC09C3E5 ...
Страница 25: ...25 7 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Страница 26: ...26 8 Wiring Connection Diagram 8 1 WH MDC09C3E5 ...
Страница 27: ...27 ...
Страница 28: ...28 8 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Страница 29: ...29 ...
Страница 30: ...30 9 Electronic Circuit Diagram 9 1 WH MDC09C3E5 ...
Страница 31: ...31 ...
Страница 32: ...32 9 2 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 ...
Страница 33: ...33 ...
Страница 34: ...34 10 Printed Circuit Board 10 1 Water System 10 1 1 Main Printed Circuit Board ...
Страница 35: ...35 10 1 2 Solar Printed Circuit Board Optional ...
Страница 36: ...36 10 2 Refrigerant System 10 2 1 Main Printed Circuit Board ...
Страница 37: ...37 10 2 2 Capacitor Printed Circuit Board 10 2 3 Noise Filter Printed Circuit Board ...
Страница 38: ...38 11 Installation Instruction Monobloc Unit Dimension Diagram ...
Страница 39: ...39 Main Components ...
Страница 52: ...52 Solar Priority is Set Solar Priority is Not Set ...
Страница 55: ...55 Heat Tank Heating No Priority Solar Priority Set ...
Страница 56: ...56 Heat Tank Heating No Priority Solar Priority Not Set ...
Страница 66: ...66 Solar Priority Not Set Heat Tank Mode Heating Priority Set ...
Страница 67: ...67 Tank Mode Solar Priority Set Solar Priority Not Set ...
Страница 115: ...115 17 3 To Remove The Cabinet Rear Plate 17 4 To Remove Pressure Gauge 17 5 To Remove RCCB ...
Страница 118: ...118 17 10 To Remove Bottle Complete When reinstall the water pipe use grease or water at the joining ...
Страница 130: ...130 ...
Страница 134: ...134 19 2 WH MDC09C3E5 WH MDC12C6E5 WH MDC14C6E5 WH MDC16C6E5 Water System ...