Items to Check Before the Test Run
(1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crankcase heater.
(2) Fully open the closed valves on the liquid tube and gas tube sides.
Preparation for Test Run
Even if the remote controller sensor is selected, the sensor will be automatically switched to the indoor unit
body sensor if no temperature signal has been received from the remote controller for 10 minutes.
Install the remote controller in a position where the signal can be reliably received by the unit.
When group control is engaged, be sure to use the body sensor.
Temperature sensors are contained in the indoor unit and wireless remote controller.
One or the other of the temperature sensors is used for operation.
If
sensor is used for operation.
To switch to the remote controller sensor, open the remote controller cover and press the SENSOR button once.
(body sensor) appears on the LCD display of the wireless remote controller, then the indoor unit body
N OT E
Switching the temperature sensor
Face the remote controller toward the receiver (on the main unit).
The signal can be received up to a distance of approximately 8 m.
Use this distance as a guide.
This distance may vary somewhat depending on the battery capacity and other factors.
Be sure that there are no objects between the remote controller and the receiver which may block the signal.
The unit beeps when a signal is received correctly. (For operation start only, the unit beeps twice.)
Do not drop, throw, or wash the remote controller.
Do not place the remote controller in locations exposed to direct sunlight or nearby a stove.
Using the remote controller
The
(body sensor) display disappears and the remote control sensor is used for operation.
<Indicators>
OPERATION
STANDBY
TIMER
OPERATION TIMER STANDBY
Receiver
SM830211-07̲PAC-i.indb 328
SM830211-07̲PAC-i.indb 328
2013/09/17 22:48:06
2013/09/17 22:48:06
Содержание U-100PEY1E5
Страница 536: ... MEMO 1 526 ...
Страница 540: ... MEMO 2 4 ...
Страница 543: ...3 3 3 3 1 Indoor Units 4 Way Cassette 60 60 Type S 36PY1E5 S 45PY1E5 S 50PY1E5 Electric Wiring Diagram 䡵 ...
Страница 547: ...3 7 3 3 1 Indoor Units Wall Mounted Type S 36PK1E5 S 45PK1E5 S 50PK1E5 S 60PK1E5 S 71PK1E5 Electric Wiring Diagram 䡵 ...
Страница 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Страница 550: ...3 10 3 3 1 Indoor Units Ducted Type S 60PN1E5 S 71PN1E5 S 100PN1E5 S 125PN1E5 S 140PN1E5 Electric Wiring Diagram ...
Страница 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Страница 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Страница 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Страница 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Страница 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Страница 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Страница 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Страница 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Страница 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Страница 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Страница 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 596: ...4 36 4 HIC PCB continued A746847 U 125PE1E5 U 140PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 738: ... MEMO 8 34 ...
Страница 739: ...201309 ...