8-32
8
1. The Self-Diagnosis Function Display and What is Detected
8-21. Common to All Models
Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote control is
connected. For information on how to deal with the alarms, refer to the Mounting Instructions for the indoor unit or to
Test Run or servicing materials.
: Off /
: On /
: Blinking (0.5 sec. intervals)
Error Detected
WL Remote Control LED Displa
y
Alarm Display
Run
Timer
Standby
Blinking
Communication error in the remote control
circuit
E01–E03, E08–E14, E17, E18
Communication error either in the in/
outdoor operation line or the sub-bus of
the outdoor unit
E04–E07, E15, E16, E19–E31
Operation of indoor protection device
P01, P09–P14
Alternately
Operation of outdoor protection device
P02–P08, P15–P31
Alternately
Error in the indoor thermistor
F01–F03, F10–F11
Alternately
Error in the outdoor thermistor
F04–F09, F12–F28
Alternately
Error in the indoor EEPROM
F29
Simultaneously
Error in the outdoor EEPROM
F30, F31
Simultaneously
Error related to the compressor
H01–H31
Error in indoor settings
L01–L03 L05–L09
Simultaneously
Error in outdoor settings
L04, L10–L31
Simultaneously
Inconsistency in Air/Heat (Including an auto-temp setting for a model without
auto-temp settings)
Alternately
Oil Alarm (Same as operation of outdoor protection device)
Alternately
Test Run
Simultaneously
When using CZ-RWSC2
If you have either an outdoor maintenance remote control or
a wired remote control and a service checker special wiring
(623 178 5082: for service use) at hand, you can get more
detailed information about an alarm by connecting one to the service
connecter as in the diagram. For information such as how to connect
to receivers, etc., refer to the Users Manual that came attached with
the service checker special wiring.
Service
Connector
Sensor Button
2. Room Temperature Sensor Settings
Common to All Models
The indoor unit and the wireless remote control are equipped with
indoor temperature sensors. The sensing of indoor temperature
works via one of them.
When the unit is shipped, it is set to the indoor unit, but to switch
to the remote control, press the sensor button (diagram at right)
inside the remote control’s cover and then check to make sure that
Main Sensor on the LCD screen goes off.
Even when the Sensor switch has been set to the remote
control, if the unit does not receive any room temperature
data from the remote control for ten minutes, it automatically
switches back to the indoor unit sensor, so be sure to install
the remote control facing the receiver.
NOTE
Fig. 8-42
Fig. 8-43
Sec8.indd 30
2012/02/28 16:14:03
SM830211-07̲PAC-i.indb 32
SM830211-07̲PAC-i.indb 32
2013/09/17 23:03:39
2013/09/17 23:03:39
Содержание U-100PEY1E5
Страница 536: ... MEMO 1 526 ...
Страница 540: ... MEMO 2 4 ...
Страница 543: ...3 3 3 3 1 Indoor Units 4 Way Cassette 60 60 Type S 36PY1E5 S 45PY1E5 S 50PY1E5 Electric Wiring Diagram 䡵 ...
Страница 547: ...3 7 3 3 1 Indoor Units Wall Mounted Type S 36PK1E5 S 45PK1E5 S 50PK1E5 S 60PK1E5 S 71PK1E5 Electric Wiring Diagram 䡵 ...
Страница 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Страница 550: ...3 10 3 3 1 Indoor Units Ducted Type S 60PN1E5 S 71PN1E5 S 100PN1E5 S 125PN1E5 S 140PN1E5 Electric Wiring Diagram ...
Страница 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Страница 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Страница 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Страница 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Страница 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Страница 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Страница 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Страница 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Страница 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Страница 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Страница 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 596: ...4 36 4 HIC PCB continued A746847 U 125PE1E5 U 140PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 738: ... MEMO 8 34 ...
Страница 739: ...201309 ...