4-7
4
4-5. Automatic Heating/Cooling Control
Ԙ
The operating mode is selected according to the set temperature and room temperature when the
operation is started.
Room temperature > set temperature in remote controller – 1˚C
→
Cooling mode
Room temperature < set temperature in remote controller – 1˚C
→
Heating mode
ԙ
The set temperature is corrected according to the operating mode. The correction temperature is +2
degrees in cooling mode and -2 degrees in heating mode at the time of factory shipment.
The correction value is different depending on the model. Refer to “4-11. Parameter” for details.
Corrected cooling temperature – control temperature for cooling
Corrected heating temperature – control temperature for heating
When setting temperature in remote controller is 20˚C in the cooling mode (at shipment) :
Control temp. for cooling
22˚C
Set temp. in remote controller
20˚C
Control temp. for heating
18˚C
㽴
Condition for mode change
Heating
→
Cooling: Room temperature > Control temperature for c 0.5 degree
Cooling
→
Heating: Room temperature < Control temperature for heating -1.0 degree
When setting temperature in remote controller is 20˚C in the cooling mode :
Heating
Heating thermostat OFF Cooling
Cooling thermostat OFF
Heating
continues for 10
minutes regardless
of temp. condition.
Then, the mode
changes to cooling.
The heating
thermostat OFF
continues for 10
minutes regardless
of temp. condition.
Then, the mode
changes to heating.
The cooling
thermostat OFF
Set temp. in remote controller
Control temp. for cooling
+2deg
Control temp. for heating
+2.5deg
Temp. for switching to cooling
Temp. for switching to heating
-2deg
-3deg
Heating thermostat OFF temp.
-1deg
Cooling thermostat OFF temp.
+1deg
For settings at the time of factory shipment, refer to “4-11. Parameter”.
SM830211-07̲PAC-i.indb 7
SM830211-07̲PAC-i.indb 7
2013/08/06 21:55:41
2013/08/06 21:55:41
Содержание U-100PEY1E5
Страница 536: ... MEMO 1 526 ...
Страница 540: ... MEMO 2 4 ...
Страница 543: ...3 3 3 3 1 Indoor Units 4 Way Cassette 60 60 Type S 36PY1E5 S 45PY1E5 S 50PY1E5 Electric Wiring Diagram 䡵 ...
Страница 547: ...3 7 3 3 1 Indoor Units Wall Mounted Type S 36PK1E5 S 45PK1E5 S 50PK1E5 S 60PK1E5 S 71PK1E5 Electric Wiring Diagram 䡵 ...
Страница 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Страница 550: ...3 10 3 3 1 Indoor Units Ducted Type S 60PN1E5 S 71PN1E5 S 100PN1E5 S 125PN1E5 S 140PN1E5 Electric Wiring Diagram ...
Страница 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Страница 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Страница 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Страница 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Страница 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Страница 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Страница 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Страница 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Страница 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Страница 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Страница 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 596: ...4 36 4 HIC PCB continued A746847 U 125PE1E5 U 140PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Страница 738: ... MEMO 8 34 ...
Страница 739: ...201309 ...