Specifications
FP2 S
−
LINK Unit
2
−
8
2.3
Specifications
2.3
Specifications
Item
Specifications
FP2 S
−
LINK unit
CPU with S
−
LINK
Ambient operating temperature
0 to 55
°
C
Ambient storage temperature
−
20 to 70
°
C
Ambient operating humidity
30 to 85% RH (with no condensation)
Ambient storage humidity
30 to 85% RH (with no condensation)
Breakdown voltage
500V AC between S
−
LINK terminal
block and ground, for 1 minute
1500V AC between S
−
LINK terminal
block and AC outer terminal, for 1
minute
500V AC between S
−
LINK terminal
block and ground, for 1 minute
1500V AC between AC outer terminal
and ground, for 1 minute
500V AC between DC outer terminal
and ground, for 1 minute
1500V AC between S
−
LINK terminal
block and AC outer terminal, for 1
minute
Insulation resistance
100M
Ω
min. between S
−
LINK termi-
nal block and ground (using 500V DC
mega ohmmeter)
100M
Ω
min. between S
−
LINK termi-
nal block and AC outer terminal (us-
ing 500V DC mega ohmmeter)
100M
Ω
min. between S
−
LINK termi-
nal block and ground (using 500V DC
mega ohmmeter)
100M
Ω
min. between AC outer termi-
nal and ground (using 500V DC mega
ohmmeter)
100M
Ω
min. between S
−
LINK termi-
nal block and AC outer terminal (us-
ing 500V DC mega ohmmeter)
Breakdown vibration
10 to 55Hz, 1 sweep/minute Multi
−
amplitude 0.75mm, 10 minutes each in X,
Y, Z directions
Breakdown shock
98m/s
2
min., 4 times each in X, Y, Z directions
Usage environment
No corrosive gases. No heavy dust.
Current consumption
130mA max.
670mA max.
Main unit weight
Approx. 120g
Approx. 250g
Содержание S-Link FP2
Страница 1: ......
Страница 8: ...Selecting the Right Equipment FP2 S LINK Unit 1 2 ...
Страница 16: ...Specifications FP2 S LINK Unit 2 2 ...
Страница 26: ...I O Assignments FP2 S LINK Unit 3 2 ...
Страница 36: ...Construction and Wiring FP2 S LINK Unit 4 2 ...
Страница 42: ...Operation FP2 S LINK Unit 5 2 ...
Страница 55: ...Chapter 6 Shared Memory 6 1 Configuration of the Shared Memory 6 3 6 2 Shared Memory Reading Program 6 4 ...
Страница 56: ...Shared Memory FP2 S LINK Unit 6 2 ...
Страница 62: ...Shared Memory FP2 S LINK Unit 6 8 6 2 Shared Memory Reading Program ...
Страница 64: ...What To Do If An Error Occurs FP2 S LINK Unit 7 2 ...
Страница 70: ...What To Do If An Error Occurs FP2 S LINK Unit 7 8 7 3 Judging Error Displays ...
Страница 72: ...Appendix FP2 S LINK Unit 8 2 ...
Страница 78: ...Appendix FP2 S LINK Unit 8 8 8 2 S LINK Address Quick Reference Table ...
Страница 80: ...FP2 S LINK Unit Record of changes R 2 ...
Страница 81: ......