Construction and Wiring
FP2 S
−
LINK Unit
4
−
4
4.1
Wiring Methods for S
−
LINK Main Unit
Use an appropriate tool to tighten the terminal block.
When tightening the terminal block, a screwdriver designed exclusively for that purpose
should be used (see table below). The tightening torque should be 0.22 to 0.25 N
−
m (2.3
to 2.5 kgf
−
cm).
Appropriate tool (blade width 0.4
×
2.5)
Panasonic Electric Works SUNX Co., Ltd.
Order no.
Phoenix Contact Co. model no.
AFP0806
Model no.
Product no.
SZS 0.4
×
2.5
1205037
4.1.2
Standard Wiring
Only the “Out A (main cable)” of the S
−
LINK terminal block is used.
Terminal name
Color of
connecting cable
Out A
(Main cable)
24V
Brown
(Main cable)
0V
Blue
D
White
G
Black
Note
For information on power supply wiring, refer to section “4.2
S
−
LINK Power Supply”. For information on wiring and connecting
S
−
LINK devices, refer to the “S
−
LINK Construction Manual.”
Out A
(main cable)
Standard wiring
S
−
LINK exclusive
flat cable
S
−
LINK unit
Power supply cable
Содержание S-Link FP2
Страница 1: ......
Страница 8: ...Selecting the Right Equipment FP2 S LINK Unit 1 2 ...
Страница 16: ...Specifications FP2 S LINK Unit 2 2 ...
Страница 26: ...I O Assignments FP2 S LINK Unit 3 2 ...
Страница 36: ...Construction and Wiring FP2 S LINK Unit 4 2 ...
Страница 42: ...Operation FP2 S LINK Unit 5 2 ...
Страница 55: ...Chapter 6 Shared Memory 6 1 Configuration of the Shared Memory 6 3 6 2 Shared Memory Reading Program 6 4 ...
Страница 56: ...Shared Memory FP2 S LINK Unit 6 2 ...
Страница 62: ...Shared Memory FP2 S LINK Unit 6 8 6 2 Shared Memory Reading Program ...
Страница 64: ...What To Do If An Error Occurs FP2 S LINK Unit 7 2 ...
Страница 70: ...What To Do If An Error Occurs FP2 S LINK Unit 7 8 7 3 Judging Error Displays ...
Страница 72: ...Appendix FP2 S LINK Unit 8 2 ...
Страница 78: ...Appendix FP2 S LINK Unit 8 8 8 2 S LINK Address Quick Reference Table ...
Страница 80: ...FP2 S LINK Unit Record of changes R 2 ...
Страница 81: ......
Страница 82: ......