11.10.5 INDOOR UNIT DRAIN PIPING
•
Drain piping must have down-slope (1/50 to
1/100); be sure not to provide up-and-down slope
to prevent reversal flow.
•
During drain piping connection, be careful not to
exert extra force on the drain port at the indoor
unit.
•
The outside diameter of the drain connection at
the indoor unit is 16 mm.
Piping material: Polyvinyl chloride pipe VP-16 and
pipe fittings.
•
Be sure to perform heat insulation on the drain
piping.
Heat insulation material: Polyethylene foam with
thickness more than 8 mm (local supply).
Upward routing
Pipe clamp
Indoor
unit
Trap
Down-slope
11.10.6 HEAT
INSULATION
Caution
Be sure to perform heat insulation on the drain, liquid and gas piping. Imperfection in heat insulation work leads to water
leakage.
1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C).
Overlap with heat
insulator for piping.
Indoor
unit
Band
(Accessory)
Heat insulator
for piping
(Local supply)
Heat insulator
(Accessory)
Hose clip (Accessory)
Heat insulator (Local
supply) (The thickness
must be at least 8 mm.)
Flexible hose with
heat insulator
(Accessory)
PVC pipe
(O.D. ø16)
(Local supply)
To be glued
It may be required to take off this part for checking
or servicing the drain up motor. Please do not glue.
Make sure that there is no clearance here.
2. Precautions in high humidity circumstance.
This air conditioner has been tested according to the “JIS Standard Conditions with Mist” and have been
confirmed that there are no faults. However, if it is operated for a long time in high humid atmosphere (dew point
temperature: more than 23°C), water drops are liable to fall. In this case, add heat insulation material according
to the following procedure:
•
Heat insulation material to be prepared…
Adiabatic glass wool with thickness 10 to 20
mm.
•
Stick glass wool on all air conditioners that are
located in ceiling atmosphere.
•
In addition to the normal heat insulation
(thickness: more than 8 mm) for refrigerant
piping (gas piping: thick piping) and drain
piping, add a further of 10 mm to 30 mm
thickness material.
Pipe down
Indoor
unit
Pipe
Putty
Trap
Incision
Drain pipe
✳
Put the incision at the trap part of the heat insulator
(for water drain)
Wall seal
•
When the outdoor unit is installed on a higher position than the indoor unit, install the trap so as not to instill
rain water into the wall by transmitting in piping.
•
Stuff the space among piping, the electric wire, and the drain hose with “Putty” and seal the penetration wall
hole.
Make sure that rain water do not instill into the wall.
Содержание S-22KA1E5S
Страница 45: ...45 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5...
Страница 46: ...46 4 2 60 x 60 Cassette Type Indoor Unit 4 2 1 S 22YA1E5 S 28YA1E5 S 36YA1E5 S 45YA1E5 S 56YA1E5...
Страница 47: ...47 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5...
Страница 48: ...48 4 3 2 S 100UA1E5 S 125UA1E5...
Страница 49: ...49 4 4 Slim Hide Away Type Indoor Unit 4 4 1 S 22NA1E5 S 28NA1E5 S 32NA1E5 S 36NA1E5 S 45NA1E5 S 56NA1E5...
Страница 50: ...50 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5...
Страница 51: ...51 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5...
Страница 52: ...52 4 5 3 S 100MA1E5 S 125MA1E5...
Страница 53: ...53 4 6 Outdoor Unit 4 6 1 U 8EA1E8 U 10EA1E5...
Страница 54: ...54 5 Refrigeration Cycle Diagram...
Страница 58: ...58 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series...
Страница 59: ...59 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series...
Страница 60: ...60 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series...
Страница 61: ...61 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series...
Страница 62: ...62 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series...
Страница 63: ...63 7 6 Outdoor Unit EA1E8 Series...
Страница 64: ...64 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series...
Страница 65: ...65...
Страница 66: ...66 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series...
Страница 67: ...67...
Страница 68: ...68 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series...
Страница 69: ...69...
Страница 70: ...70 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series...
Страница 71: ...71...
Страница 72: ...72 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series...
Страница 73: ...73...
Страница 74: ...74 8 6 Outdoor Unit EA1E8 Series...
Страница 75: ...75...
Страница 77: ...77 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE...
Страница 82: ...82 9 6 2 Inverter PCB CN AC CN RY2 CN RY1 CN FM2 CN COM FG DCN CN FM1 DCP W V U...
Страница 231: ...231 19 Operation Range...
Страница 233: ...233 21 Outdoor Unit Cooling Heating Capacity and Power Input 21 1 U 8EA1E8...
Страница 234: ...234...
Страница 235: ...235 21 2 U 10EA1E8...
Страница 236: ...236...
Страница 302: ...302 27 8 Outdoor Unit U 10EA1E8...