11.8.5 INDOOR UNIT DRAIN PIPING
•
Drain piping must have down-slope (1/50 to
1/100); be sure not to provide up-and-down slope
to prevent reversal flow.
•
During drain piping connection, be careful not to
exert extra force on the drain port at the indoor
unit.
•
The outside diameter of the drain connection at
the indoor unit is 32 mm.
Piping material: Polyvinyl chloride pipe VP-25 and
pipe fittings.
•
Be sure to perform heat insulation on the drain
piping.
Heat insulation material: Polyethylene foam with
thickness more than 8 mm (local supply).
Upward routing
Pipe clamp
Indoor
unit
Trap
Down-slope
•
The height of drain may be possible up to 750 mm.
Down-slope (1/50 ~ 1/100)
Drain port
750 m
m
or
les
s
Indoor unit
Elbow
Elbow
•
When drain set piping, install as shown in the
figure below.
Drain Test
The air conditioner uses a drain up motor to drain water. Use the following procedure to test the drain up motor
operation.
•
Connect the main drain pipe to exterior and leave
it provisionally until the test comes to an end.
•
Feed water to the flexible drain hose and check
the piping for leakage.
•
Be sure to check the drain up motor for normal
operating and noise when electric wiring is
complete.
•
When the test is complete, connect the flexible
drain hose to the drain port.
Feed water
Drain hose
Drain up motor
Glue the joint
Drain hose connection
Use the clip (accessory)
Main drain
pipe
Drain
port
11.8.6 HEAT INSULATION
Caution
Be sure to perform heat insulation on the drain, liquid and gas piping. Imperfection in heat insulation work leads to water
leakage.
1. Use the heat insulation material for the refrigerant piping which has an excellent heat-resistance (over 120°C).
Overlap with heat
insulator for piping.
Indoor
unit
Band
(Accessory)
Heat insulator
for piping
(Local supply)
Heat insulator
(Accessory)
Hose clip (Accessory)
Heat insulator (Local
supply) (The thickness
must be at least 8 mm.)
Flexible hose with
heat insulator
(Accessory)
PVC pipe
(O.D. ø25)
(Local supply)
To be glued
It may be required to take off this part for checking
or servicing the drain up motor. Please do not glue.
Make sure that there is no clearance here.
Содержание S-22KA1E5S
Страница 45: ...45 4 1 2 S 56KA1E5 S 63KA1E5 S 71KA1E5...
Страница 46: ...46 4 2 60 x 60 Cassette Type Indoor Unit 4 2 1 S 22YA1E5 S 28YA1E5 S 36YA1E5 S 45YA1E5 S 56YA1E5...
Страница 47: ...47 4 3 95 x 95 Cassette Type Indoor Unit 4 3 1 S 63UA1E5 S 71UA1E5 S 90UA1E5...
Страница 48: ...48 4 3 2 S 100UA1E5 S 125UA1E5...
Страница 49: ...49 4 4 Slim Hide Away Type Indoor Unit 4 4 1 S 22NA1E5 S 28NA1E5 S 32NA1E5 S 36NA1E5 S 45NA1E5 S 56NA1E5...
Страница 50: ...50 4 5 Low Static Pressure Hide Away Type Indoor Unit 4 5 1 S 45MA1E5 S 56MA1E5...
Страница 51: ...51 4 5 2 S 63MA1E5 S 71MA1E5 S 90MA1E5...
Страница 52: ...52 4 5 3 S 100MA1E5 S 125MA1E5...
Страница 53: ...53 4 6 Outdoor Unit 4 6 1 U 8EA1E8 U 10EA1E5...
Страница 54: ...54 5 Refrigeration Cycle Diagram...
Страница 58: ...58 7 Wiring Connection Diagram 7 1 Wall Mounted Type Indoor Unit KA1E5 Series...
Страница 59: ...59 7 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series...
Страница 60: ...60 7 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series...
Страница 61: ...61 7 4 Slim Hide Away Type Indoor Unit NA1E5 Series...
Страница 62: ...62 7 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series...
Страница 63: ...63 7 6 Outdoor Unit EA1E8 Series...
Страница 64: ...64 8 Electronic Circuit Diagram 8 1 Wall Mounted Type Indoor Unit KA1E5 Series...
Страница 65: ...65...
Страница 66: ...66 8 2 60 x 60 Cassette Type Indoor Unit YA1E5 Series...
Страница 67: ...67...
Страница 68: ...68 8 3 95 x 95 Cassette Type Indoor Unit UA1E5 Series...
Страница 69: ...69...
Страница 70: ...70 8 4 Slim Hide Away Type Indoor Unit NA1E5 Series...
Страница 71: ...71...
Страница 72: ...72 8 5 Low Static Pressure Hide Away Type Indoor Unit MA1E5 Series...
Страница 73: ...73...
Страница 74: ...74 8 6 Outdoor Unit EA1E8 Series...
Страница 75: ...75...
Страница 77: ...77 9 1 3 Receiver PCB CN DISP 9 1 4 Error Code Display PCB CN CODE...
Страница 82: ...82 9 6 2 Inverter PCB CN AC CN RY2 CN RY1 CN FM2 CN COM FG DCN CN FM1 DCP W V U...
Страница 231: ...231 19 Operation Range...
Страница 233: ...233 21 Outdoor Unit Cooling Heating Capacity and Power Input 21 1 U 8EA1E8...
Страница 234: ...234...
Страница 235: ...235 21 2 U 10EA1E8...
Страница 236: ...236...
Страница 302: ...302 27 8 Outdoor Unit U 10EA1E8...