2-7. Table of Self-Diagnostic Functions and Corrections
Wired remote controller displa
y
Indoor unit
receiver lamp
Caus
e
Correction
1:1 connection (single type)
Group connection
Simultaneous-operation multi system
(flexible combination)
Control by main-sub remote controllers
Nothing is
displaye
d
Nothing is
displaye
d
Remote controller is not connected correctly. Indoor unit power is not ON
.
Remote controller is not connected with indoor unit correctl
y
Indoor unit power is not ON
.
Same at left
Same at left
Same at left
Same at left
Same at left
Same at left
Same at left
Same at left
Same at left
Same at left
Same at left
Same at left
Connect the remote controller correctly
.
Turn ON the indoor unit power
.
E0
1
displaye
d
Operating lamp is blinking.
Automatic address setting has not been completed. Inter-unit control wiring is cut or is not
connected correctly. Remote controller is not connected correctly (remote controller receiving failure).
Automatic address setting has not
been completed. Inter-unit control wiring is cut or is
not connected correctly
.
Remote controller is not connected with indoor unit correctly.
Same at left
Check the remote controller and inter- unit control wiring. Perform automatic address setting
(See
2-8-3)
.
E0
2
displaye
d
displaye
d
displaye
d
Remote controller is not connected correctly (failure in transmission from
remote controller to indoor unit)
.
Remote controller is not connected with indoor unit correctly.
Same at left
Connect the remote controller correctly
.
E0
9
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
2 remote
controllers are set as the main
remote controller.
Refer to 2-8-4 Main-sub remote
Control, and make the correct settings
.
E1
4
—
—
—
—
—
—
—
—
—
—
—
—
Remote controller communication wiring is cut or is not connecte
d
correctly
.
Check the remote controller communi
-
cation wiring. Perform automatic address setting again.
E0
4
displaye
d
Standby lamp is
blinking.
Indoor-outdoor inter-unit wiring is not
connected correctly.
Same at left
Same at left
Connect the wiring correctly
.
E0
6
displaye
d
Indoor-outdoor inter-unit wiring is
cut or is not connected correctly
.
Same at left
Refer to 2-8 System Control, and make
the correct settings
.
E1
5
displaye
d
Indoor unit capacity is too low.
Same at left
Same at left
Check that the total capacities of
the indoor and outdoor units are appropriate
.
E1
6
displaye
d
Indoor unit capacity is too high.
E2
0
displaye
d
No serial signal is being received at all from the indoor units
.
Check that the indoor unit power is ON, and that the inter-unit control wiring is
connected correctly
.
P0
5
displaye
d
Operation lamp
and Standby
lamp are blinking alternately.
Reversed phase in the outdoor unit single-phase or open phase in the outdoor unit 3-phase power
.
Insufficient gas
Reversed phase in the outdoor
unit single phase or open phase in the 3-phase power at one of the outdoor units in the group.
Reversed phase in the outdoor unit single-phase or open phase in the outdoor unit 3-phase power
.
CT sensor is disconnected or there is a problem with the circuit
.
Reverse 2 phases of the outdoor unit 3-phase power and connect them
correctly
.
Check that the CT sensor is not
disconnected, and make sure it is
inserted. Fill up the gas appropriately
.
L0
2
displaye
d
L1
3
displaye
d
displaye
d
Both the Operation lamp
and Standby
lamp are blinking together
.
Indoor-outdoor unit type mismatch.
Same at left
Same at left
——————
Check that the indoor and outdoor unit types are correct
.
L0
7
Remote controller communication wiring is connected to the indoor
unit, however it is set for individual
operation.
Perform automatic address setting (See 2-8-3).
P0
9
displaye
d
Timer lamp and Standby lamp are blinking alternately.
The indoor unit ceiling panel connector is not connected correctly.
Ceiling panel connector at one of
the indoor units in the group is not
connected correctly.
Indoor unit ceiling panel connector is not connected correctly
.
Connect the indoor unit ceiling panel
connector correctly
.
P1
2
displaye
d
Indoor unit DC fan trouble.
DC fan trouble at one of the indoor
units in the group.
Indoor unit fan trouble.
Check whether the fan holder is loose. Check the wiring between the DC fan and the PCB.
P1
5
displaye
d
Operation lamp
and Standby
lamp are blinking alternately.
No gas
Same at left
Same at left
——————
Check the refrigerant cycle (for gas
leaks).
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
SM830252-00_欧州_Single_天埋.indb 5
16/08/26 10:42:23
Содержание S-200PE2E5
Страница 70: ...1 64 MEMO SM830252 00_欧州_Single_天埋 indb 64 16 08 26 10 40 29 ...
Страница 86: ... MEMO 3 4 SM830252 00_欧州_Single_天埋 indb 4 16 08 08 13 11 45 ...
Страница 166: ... MEMO 7 16 SM830252 00_欧州_Single_天埋 indb 16 16 08 27 8 24 20 ...
Страница 188: ...201608 SM830252 00_欧州_Single_天埋 indb 1 16 08 10 15 45 43 ...