7
7
Item
code
Item
Setting data
No.
Description
No.
Description
No.
Description
Type
0000
0001
0002
0003
0005
0006 High Static Pressure
Ducted (E2)
0007
0008
0010
0011
Indoor unit
capacity
0001
0003
0005
0007
0009
0011
0012
0015
0017
0020
0021
224
0023
280
System
address
0001 Unit No. 1
0002 Unit No. 2
0003 Unit No. 3
0030 Unit No. 30
0099 Not set
Indoor unit
address
0001 Unit No. 1
0002 Unit No. 2
0003 Unit No. 3
0064 Unit No. 64
0099 Not set
Group control
address
0000 Individual (1:1 = Indoor unit with no group wiring)
0001 Main unit (One of the group-control indoor units)
0002 Sub unit (All group-control indoor units except for main unit)
0099 Not set
Cooling intake
temperature
shift
–010 Shifts intake temperature 10°C down.
–009 Shifts intake temperature 9°C down.
–001 Shifts intake temperature 1°C down.
0000 No intake temperature shift
0001 Shifts intake temperature 1°C up.
0009 Shifts intake temperature 9°C up.
0010 Shifts intake temperature 10°C up.
Automatic
stop time after
operation start
0000 Function disabled
0001 Stops automatically 5 minutes after operation starts.
0002 Stops automatically 10 minutes after operation starts.
Can be set
in 5-minute
units.
*
0123 Stops automatically 615 minutes after operation starts.
0124 Stops automatically 620 minutes after operation starts.
0125 Stops automatically 625 minutes after operation starts.
7-4. List of Detailed Setting Items
Optional Controller
Remote Controller Functions
5. Detailed Settings Function
A
°
°
“ ”, unit No. “ ”, item code “ ,” and
settings data “ ” are displayed blinking on the
remote controller LCD display (Fig. 7-2). At this time,
the indoor unit fan begins operating.
This allows the system address, indoor unit address, and other settings to be made for the individual or
group-control indoor unit to which the remote controller used for detailed settings is connected.
When detailed settings mode is engaged, operation stops at the individual or group-control indoor unit where the
remote controller used for detailed settings is connected. Simple settings items can also be set at this time.
Press and hold the , and buttons
simultaneously for 4 seconds or longer.
If group control is in effect, press the button and
select the address (unit No.) of the indoor unit to set.
At this time, the fan at the indoor unit begins operating.
*If unit No. “ ” is displayed, the same setting
will be made for all indoor units.
Press the temperature setting / buttons to
select the item code to change.
Press the timer time / buttons to select the
desired setting data.
*For item codes and setting data, refer to the
following page.
Press the button. (The display stops blinking
and remains lit, and setting is completed.)
Press the button to return to normal remote
controller display.
(7)
(1)
(6)
(3)
(2)
(4)
(5)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
7-5
SM830252-00_欧州_Single_天埋.indb 5
16/08/27 8:24:16
Содержание S-200PE2E5
Страница 70: ...1 64 MEMO SM830252 00_欧州_Single_天埋 indb 64 16 08 26 10 40 29 ...
Страница 86: ... MEMO 3 4 SM830252 00_欧州_Single_天埋 indb 4 16 08 08 13 11 45 ...
Страница 166: ... MEMO 7 16 SM830252 00_欧州_Single_天埋 indb 16 16 08 27 8 24 20 ...
Страница 188: ...201608 SM830252 00_欧州_Single_天埋 indb 1 16 08 10 15 45 43 ...